Set-point availability varies based on unit configuration.
Control Variable
Default
Min.
Max.
Notes
Pressure Control
Condenser Type
Condenser Fan Control
Condenser Fan Control
Water Valve Control
Cooling
105.0°F
80.0°F
140.0°F
Dehumidifying
115.0°F
80.0°F
140.0°F
Offset
5.0 Δ°F
1.0 Δ°F
20.0 Δ°F
AHPC 1.0
Heating
50.0°F
40.0°F
60.0°F
Offset
2.0 Δ°F
1.0 Δ°F
10.0 Δ°F
AHPC 1.0
Pressure Control - Water Valve
Cooling Min. Position
20%
0%
100%
WSHP
Heating Min. Position
20%
0%
100%
WSHP
Off Position
100%
0%
100%
WSHP
Condenser Fan Minimum
Speed
25%
0%
100%
Table 33: Refrigeration Pressure Control Set-Points Data Table.
Table 34: Refrigeration Heat Pump Control Set-points Data Table.
Control Variable
Default
Min.
Max.
Notes
WSHP Cold Start
OAT Enable
30.0°F
0.0°F
60.0°F
Duration
60 sec.
0 sec.
600 sec.
WSHP Fluid Freeze Set-point
32.0°F
0.0°F
32.0°F
ASHP Low Ambient Lockout
17.0°F
10.0°F
50.0°F
WSHP Low Saturated Suction
Lockout
-15.0°F
-30.0°F
0.0°F
Heat Pump Defrost
WSHP Cancel Set-point
95.0°F
55.0°F
110.0°F
ASHP Cancel Set-point
60.0°F
55.0°F
80.0°F
Max. Time
10 min.
5 min.
20 min.
Table 35: Damper Control Set-points Data Table.
Control Variable
Default
Min.
Max.
Notes
Fan Damper Delay
30 sec.
0 sec.
300 sec.
Outside Damper
Minimum
0%
0%
100%
CO
2
Minimum
20%
0%
100%
Maximum
100%
0%
100%
Outside Damper Airflow Set-
point
0 CFM
0 CFM
999999 CFM
Economizer Mode Selected
Outside Dry Bulb
Disabled, Outside Dry Bulb, Outside Enthalpy,
Comparative Dry Bulb, Comparative Enthalpy
Economizer Settings
Outside Dry Bulb Set-point
65°F
50.0°F
90.0°F
Outside Enthalpy Set-point
23 Btu/lb.
15 Btu/lb.
40 Btu/lb.
Hysteresis
Temperature
2.0 Δ°F
0.0 Δ°F
10.0 Δ°F
Enthalpy
2.0 Btu/lb.
0.0 Btu/lb.
10.0 Btu/lb.
Space CO
2
Set-point
700 ppm
0 ppm
5,000 ppm
CONTROLLER
Set-Points Data Tables