Table 64: LonTalk Points List.
Access
NV Name
SNVT Type
Description
Notes
Read-Only Points, continued.
nvo
DigStatus.bit09
state.bit09
Supply Fan Status
0=Off 1=On
nvo
DigStatus.bit10
state.bit10
Exhaust Fan Status
0=Off 1=On
nvo
DigStatus.bit11
state.bit11
Heat Wheel Status
0=Off 1=On
nvo
DigStatus.bit12
state.bit12
PreHeat Enable Digital Output
0=Off 1=On
nvo
DigStatus.bit13
state.bit13
Reversing Valve Digital Output
0=Cooling 1=Heating
nvo
DigStatus.bit14
state.bit14
Occupied Status
0=Unoccupied 1=Occupied
nvo
DigStatus.bit15
state.bit15
Damper Status (OAD or RAD indicating a path of
airflow)
0=Closed 1=Open
nvo
GlobalAlarm
switch (95)
General alarm output
0=No Alarms 1=Active Alarms
nvo
ActTmpSpt
temp_p (105)
Active Temperature Set-point
Heating or Cooling Set-point
nvo
CirA_SatDschT
temp_p (105)
Circuit A Saturated Discharge Temperature
nvo
CirB_SatDschT
temp_p (105)
Circuit B Saturated Discharge Temperature
nvo
ColdCoil1Temp
temp_p (105)
Cold Coil Temperature
nvo
EntWterTempA
temp_p (105)
Leaving Water Temperature Circuit A
nvo
EntWterTempB
temp_p (105)
Leaving Water Temperature Circuit B
nvo
ExhaustTemp
temp_p (105)
Exhaust Temperature
nvo
LeavWterTempA
temp_p (105)
Entering Water Temperature Circuit A
nvo
LeavWterTempB
temp_p (105)
Entering Water Temperature Circuit B
nvo
MixedTemp
temp_p (105)
Mixed Temperature
nvo
OutsideTemp
temp_p (105)
Outside Air Temperature
nvo
SpaceTemp
temp_p (105)
Space Temperature
nvo
SupplyTemp
temp_p (105)
Supply Temperature
Write-Only Points
nvi
EconEnthTrig
enthalpy (153)
Economizer Enthalpy Enable Se-tpoint
Allow Econ when OA Enthalpy<Spt
nvi
ExhCFMSetpt
flow_p (161)
Exhaust Fan CFM Set-point
Divide desired CFM by 100.
nvi
OACFMSetpt
flow_p (161)
OAD CFM Set-point
Divide desired CFM by 100.
nvi
SupCFMSetpt
flow_p (161)
Supply Fan CFM Set-point
Divide desired CFM by 100.
nvi
DehumSetpt
lev_percent (81)
Dehumidification Set-point
%RH for Space or Return control
nvi
OADMinSetpt
lev_percent (81)
Outside Air Damper Minimum Set-point
nvi
UnocRHSetpt
lev_percent (81)
Unoccupied Dehumidification %RH Set-point
nvi
SpaceCO2Setpt
ppm (29)
Space CO2 Set-point
nvi
SpacePressSpt
press_p (113)
Space Static Pressure Set-point
nvi
SupPressSetpt
press_p (113)
Supply Duct Static Pressure Set-point
nvi
OccUnocc
switch (95)
Occupancy Command
0=Occupied 1=Unoccupied
nvi
ResetAlarms
switch (95)
Alarm Reset Command
nvi
SystemEnable
switch (95)
Master system enable/disable point
nvi
TempDeadband
temp_diff_p
(147)
Heat/Cool Spt Deadband (Space or Return control
is active)
Divided by 2.
Add/subtract to/from the
set-point
nvi
EconTempTrig
temp_p (105)
Economizer Ambient Temp Enable Set-point
Allow Econ when OAT<Spt
nvi
IADewptTrig
temp_p (105)
Inside Dewpoint Dehumidification Set-point
nvi
TempSetpt
temp_p (105)
Main Temperature Set-point
Supply, Space, or Return target
nvi
UnocCoolSetpt
temp_p (105)
Unoccupied Cooling Set-point
nvi
UnocHeatSetpt
temp_p (105)
Unoccupied Heating Set-point
CONTROLLER
LonTalk Points