Table 46: Alarm Data.
Alarm ID
Alarm Screen Line 1
Alarm Screen Line 2
Reset Type
Lockout
Action Type
Notes
1
Supply Fan 1 Run
Status Not Proven
Auto
Optional Shutdown Unit
2
Fire/Smoke Alarm
In Alarm Position
Auto
Shutdown Unit
3
Phase Protection
Relay Tripped
Auto
Shutdown Unit
4
Freeze Protection
Thermostat Tripped
Manual
Shutdown Unit
5
High Supply Duct
Static Pressure
Manual
Shutdown Unit
6
Low Return Duct
Static Pressure
Manual
Shutdown Unit
7
Outside Air Temp
Sensor Value Not Valid
Auto
Informational
8
Supply Air Temperature
Sensor Value Not Valid
Auto
Shutdown Unit
9 - 10
Cold Coil (x) Temp
Sensor Value Not Valid
Auto
Disable Cooling Ramp
11
Exhaust Air Temp
Sensor Value Not Valid
Auto
Disable Defrost
12
HX LA Temperature
Sensor Value Not Valid
Auto
Informational
13
Mixed Air Temperature
Sensor Value Not Valid
Auto
Informational
14
Preheat Leaving Temp
Sensor Value Not Valid
Auto
Disable Preheat
15
Return Air Temperature
Sensor Value Not Valid
Auto
Disable Return Temp/
Dewpoint Control
16
Space Temperature
Sensor Value Not Valid
Auto
Disable Space Temp/
Dewpoint Control
17
Return Air RH
Sensor Value Not Valid
Auto
Disable Return RH/
Dewpoint Control
18
Space RH
Sensor Value Not Valid
Auto
Disable Space RH/
Dewpoint Control
19
Supply Air RH
Sensor Value Not Valid
Auto
Disable Supply RH/
Dewpoint Control
20
HX Leaving RH
Sensor Value Not Valid
Auto
Informational
21
Outside RH
Sensor Value Not Valid
Auto
Disable OA RH/
Dewpoint Control
22 - 23
Cold Coil (x) RH
Sensor Value Not Valid
Auto
Informational
24
Exhaust Air RH
Sensor Value Not Valid
Auto
Informational
25
Preheat Leaving RH
Sensor Value Not Valid
Auto
Informational
26 -29
Low Pressure Switch
Circuit (x)
Auto until Lockout 3x in 1 hr
Disable Compressor
Circuit
30 -33
High Pressure Switch
Circuit (x)
Auto
Disable Compressor
Circuit
Manual at the
Switch
34
Damper Proving Switch
Dampers are closed
Manual
Shutdown Unit
35
Exhaust Fan 1 Run
Status Not Proven
Manual
Optional Shutdown Unit
36
Return Fan 1 Run
Status Not Proven
Manual
Optional Shutdown Unit
37
Pre-Filters are Dirty
Replace Filters
Auto
Informational
38
OA Filters are Dirty
Replace Filters
Auto
Informational
39
RA Filters are Dirty
Replace Filters
Auto
Informational
40
Cond Drain Pan Full
Check Drain
Manual
Shutdown Unit
41 - 44
Exp Board (x) Status
Board is Offline
Auto
Shutdown Unit
45 - 48
Low Pressure Switch
Circuit (x)
Auto until Lockout 3x in 1 hr
Disable Compressor
Circuit
49 - 52
High Pressure Switch
Circuit (x)
Auto
Disable Compressor
Circuit
Manual at the
Switch
53 - 64
Belimo Act (x) Comm
Actuator is Offline
Auto
Informational
65
Non Volatile Memory Er
Contact Unison
Auto
Informational
66 - 68
Supply Fan (x) Run
Status Not Proven
Manual
Optional Shutdown Unit
69 - 71
Exhaust Fan (x) Run
Status Not Proven
Manual
Optional Shutdown Unit
72 - 74
Return Fan (x) Run
Status Not Proven
Manual
Optional Shutdown Unit
75 - 78
Scavenger Fan (x) Run
Status Not Proven
Manual
Optional Shutdown Unit
79
Mixed Air RH
Sensor Value Not Valid
Auto
Informational
CONTROLLER
Alarm Data