Table 43: Network Settings Data Table, continued.
Control Variable
Default
Min.
Max.
Notes
Unit Configuration, continued.
Controls Lite Mode
Set-point
Set-point
Demand
Heating Enabled
Enabled (X)
Disabled (□)
Enabled (X)
Case Heat Installed
Not Installed (□)
Not Installed (□)
Installed (X)
Compressor Config - Stage
Read Only
Up to 8 compressors
Compressor Config- Ramp
Read Only
Up to 8 compressors
Compressor Config-Circuit
Read Only
Up to 8 compressors
Compressor Config-
Modulates
Read Only
Up to 8 compressors
Change Lead Lag Mode
Lead
Lead, Lag, w/Dehumid, Weekly
Change Lead Lag Day
Monday
Not Installed, Standard c.pCO, c.pCOe
Shows when Weekly
is selected
Ramp 1 Lead Order Stage
(1-8)
1
1
No. Comps on Ramp
Has only 1 Cooling
Ramp with up to 4
stages
Ramp 1 Lag Order Stage
(1-8)
1
1
No. Comps on Ramp
Has only 1 Cooling
Ramp with up to 4
stages
OAD Space Static Enabled
Disabled (□)
Disabled (□)
Enabled (X)
Reheat Plus Enabled
Disabled (□)
Disabled (□)
Enabled (X)
Only shows when
Reheat Plus is
Installed from
CMN
Heat Pump Defrost
Enabled
Enabled (X)
Disabled (□)
Enabled (X)
Shows when unit is
configured as
an ASHP
Max. Elec. Heat
100%
0%
100%
CMN Breakout BMS Comm
Stand Alone, Lontalk, BACnet IP, BACnet MSTP, MODBUS RTU, MODBUS IP
CMN
CMN Breakout Dmp Ctrl
100% Outside Air, Recirculating
CMN
CMN Breakout Sup Fan
Constant Volume, VAV Duct Static, Hardwired Input, BMS, CV Damper Static, Space Static,
Single Zone VAV, CFM Control
CMN
CMN Breakout CO
2
Ctrl
Disabled, Enabled
CMN
CMN Breakout Exh Fan
None, Supply Tracking, Space Pressure, Hardwired, BMS Control, CFM Control
CMN
CMN Breakout Rem Dmp
Disabled, BMS Control, CFM Control
CMN
CMN Breakout PreHeat
None, Installed
CMN
CMN Breakout Air Flow
None, Supply Inlet Cone, IAQ Damper, Supply Inlet & IAQ Damper, Exhaust Inlet Cone, Supply
& Exhaust Inlet Cones, Exhaust Inlet & IAQ Damper, SF/EF Inlets & IAQ Damper
CMN
CMN Breakout Heating
None, Gas 1 or 2 burner, Gas and Electric, Electric Only, 12:1 Gas, Hot Water, 6:1 Gas, 10:1-2
Furnace Gas
CMN
CMN Breakout Cooling
None, 1 Compressor, 2 Compressors, 4 Compressors, 1 Mod Comp, 2 Comps w/Mod, 4
Comps w/Mod, Chilled Water
CMN
CMN Breakout Enrg Rec
None, Heat Wheel w/VFD, Heat Wheel On/Off, Sensible Plate, Enthalpic Plate, Enthalpic Plate
with Bypass
CMN
CMN Breakout Economizer
None, Installed
CMN
CMN Breakout AMD Type
Standard, Thermal Dispersion
CMN
CMN Breakout Cond Fan
None, 1 Fan, 2 Fans, 3 Fans, 4 Fans, 6 Fans, 8 Fans
CMN
CMN Breakout Cond HPC
None, 1.0 A Only, 1.0 B Only, 1.0 A and B, 2.0 A Only, 2.0 B Only, 2.0 A and B, 2.0 A/B Split
CMN
CMN Breakout Heat Pump
None, ASHP, WSHP
CMN
Set-point availability varies based on unit configuration.
CONTROLLER
Network Settings Data Tables