92
Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 51:
BACnet and MODBUS Points List, continued.
Variable
Description
Active
Text
Inactive
Text
BACnet
MODBUS
Object
Instance
Object
Type
Access
Hyst Index Register
Type Size
Analog Values – Read/Write – Commandable
Temperature_Setpoint
Main Temperature Set-
point Supply, Space,
or Return Target
Temperature
1
AV
ReadCOV_
Commandable 0.1 40002 Holding
2
Temperature_Heat_
Cool_Deadband
Heat/Cool Spt Deadband
when Space or Return
control is active Clg Spt =
Offset/2 + Temp Spt Htg Spt
= Offset/2 - Temp Spt
2
AV
ReadCOV_
Commandable 0.1 40004 Holding
2
Cooling_Coil_Setpoint
Cooling Coil Leaving Air
Set-point
3
AV
ReadCOV_
Commandable 0.1 40006 Holding
2
Dehumidification_
Setpoint
"Dehumidification Set-point
%RH for Space or Return
control"
5
AV
ReadCOV_
Commandable 0.1 40010 Holding
2
Outside_Dewpoint_
Setpoint
Outside Dewpoint
Dehumidification Trigger
Setpoint
6
AV
ReadCOV_
Commandable 0.1 40012 Holding
2
Inside_Dewpoint_
Setpoint
Inside Dewpoint
Dehumidification Trigger
Setpoint
7
AV
ReadCOV_
Commandable 0.1 40014 Holding
2
Unocc_Inside_
Dewpoint_Setpoint
Unoccupied Inside Dewpoint
Dehumidification Trigger
Setpoint
9
AV
ReadCOV_
Commandable 0.1 40018 Holding
2
Unoccupied_Cooling_
Setpoint
Unoccupied Cooling Setpoint
10
AV
ReadCOV_
Commandable 0.1 40020 Holding
2
Unoccupied_
Dehumidification_
Setpoint
"Unoccupied
Dehumidification
%RH Setpoint"
11
AV
ReadCOV_
Commandable 0.1 40022 Holding
2
Unoccupied_Heating_
Setpoint
Unoccupied Heating Setpoint
12
AV
ReadCOV_
Commandable 0.1 40024 Holding
2
Economizer_Temp_
Enable_Setpoint
Economizer Ambient Temp
Enable Setpoint Allow
Econ when OAT<Spt
16
AV
ReadCOV_
Commandable 0.1 40032 Holding
2
Economizer_Enthalpy_
Enable_Setpoint
Economizer Enthalpy Enable
Setpoint Allow Econ
when OA Enthalpy<Spt
17
AV
ReadCOV_
Commandable 0.1 40034 Holding
2
Supply_Fan_CFM_
Setpoint_BMS
Supply Fan CFM Setpoint
18
AV
ReadCOV_
Commandable 0.1 40036 Holding
2
OAD_CFM_Setpoint_
BMS
OAD CFM Setpoint
19
AV
ReadCOV_
Commandable 0.1 40038 Holding
2
Outside_RH_from_BMS
Outside RH from BMS Used
when source selection is set
to BMS
21
AV
ReadCOV_
Commandable 0.1 40042 Holding
2
Outside_Temp_from_
BMS
Outside Temp from BMS
Used when source selection
is set to BMS
22
AV
ReadCOV_
Commandable 0.1 40044 Holding
2
Return_RH_from_BMS
Return RH from BMS Used
when source selection is set
to BMS
23
AV
ReadCOV_
Commandable 0.1 40046 Holding
2
CONTROLLER
BACnet and MODBUS Points