Table 56:
BACnet and MODBUS Points List, continued.
Variable
Description
Active Text Inactive
Text
BACnet
MODBUS
Object
Instance
Object
Type
Access
Hyst Index Register
Type
Size
Binary Values – Read Only
Occupied
Occupied Status
Occupied Unoccupied
16
BV
ReadCOV_
NoWrite 0 10002 Discrete
Unoccupied
Unoccupied Status
Unoccupied Occupied
17
BV
ReadCOV_
NoWrite 0 10003 Discrete
Unoccupied_Cooling_
Call
Unoccupied Cooling Call
Status
On
Off
18
BV
ReadCOV_
NoWrite 0 10004 Discrete
Unoccupied_
Dehumidification_Call
Unoccupied Dehumidification
Call Status
On
Off
19
BV
ReadCOV_
NoWrite 0 10005 Discrete
Unoccupied_Heating_
Call
Unoccupied Heating Call
Status
On
Off
20
BV
ReadCOV_
NoWrite 0 10006 Discrete
Occupied_Start
Occupied Start Command
Status
Start
Stop
21
BV
ReadCOV_
NoWrite 0 10007 Discrete
Unoccupied_Start
Unoccupied Start Command
Status
Start
Stop
22
BV
ReadCOV_
NoWrite 0 10008 Discrete
Enable_Controls
Status to indicate startup is
complete and the unit is ready
Yes
No
23
BV
ReadCOV_
NoWrite 0 10009 Discrete
Global_Alarm
General alarm point.
Optionally set to indicate
any alarm is active, or a
shutdown alarm is active
Alarm
Normal
24
BV
ReadCOV_
NoWrite 0 10010 Discrete
System_Shutdown_
Alarm
Shutdown alarm status. When
true, System Enable will be
set to false and the unit will
remain off
Alarm
Normal
25
BV
ReadCOV_
NoWrite 0 10011 Discrete
Damper_Open
Indicates there is a open air
path and the supply fan can
run
Open
Closed
26
BV
ReadCOV_
NoWrite 0 10012 Discrete
Cooling_is_On
Indicates that the unit is
cooling
Yes
No
27
BV
ReadCOV_
NoWrite 0 10013 Discrete
Economizer_is_On
Indicates that the unit is
economizing
Yes
No
28
BV
ReadCOV_
NoWrite 0 10014 Discrete
Heating_is_On
Indicates that the unit is
heating
Yes
No
29
BV
ReadCOV_
NoWrite 0 10015 Discrete
Dehumidification_
Mode_Enabled
Indicates that the unit is
dehumidifying
Yes
No
31
BV
ReadCOV_
NoWrite 0 10017 Discrete
Manual_Override_
Active
Indicates that manual
overrides are active
Active
Inactive
32
BV
ReadCOV_
NoWrite 0 10018 Discrete
Cooling_Not_Locked_
Out
Indicates that cooling is
allowed
Allowed Locked Out
33
BV
ReadCOV_
NoWrite 0 10019 Discrete
Heating_Not_Locked_
Out
Indicates that heating is
allowed
Allowed Locked Out
34
BV
ReadCOV_
NoWrite 0 10020 Discrete
Preheat_Not_
Locked_Out
Indicates that preheat is
allowed
Allowed Locked Out
36
BV
ReadCOV_
NoWrite 0 10022 Discrete
HGRH_Purging
Indicates that the hot gas
reheat value is purging
Yes
No
37
BV
ReadCOV_
NoWrite 0 10023 Discrete
CONTROLLER
BACnet and MODBUS Points