113
Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Gas Furnace
1. Turn off all electrical power to the unit before inspection and servicing.
2. The duct furnace should be inspected annually by a qualified service agency. The condition of the burners, heat exchanger, draft inducer,
vent system, operation controls and wiring should be determined. Check for obvious signs of deterioration, accumulation of dirt and debris
and any heat or water related damage. Any damaged or deteriorated parts should be replaced before the unit is put back into service.
3. Clean burners, heat exchanger, induced draft fan and vent ducts.
4. Check heat exchanger for cracks. If any are present, replace heat exchanger before putting unit back into service.
5. Check the attachment point of the duct furnace to the cabinet to verify that they are air tight.
6. Check the automatic gas valve to insure that the gas valve seat is not leaking.
7. Check the wiring connections to be sure they are secure and inspect wiring for any deterioration.
WARNING
If any of the original wiring needs to be replaced, it must be replaced with wiring material suitable for 221°F (105°C). Improper wiring may generate
heat, cause a fire, and physical injury or death.
8. Label all wires prior to disconnection when servicing the unit.
WARNING
Verify proper operation after servicing. Wiring errors can cause dangerous operation, may generate heat, cause a fire, and physical injury or death.
Verify proper operation after servicing. Wiring errors can cause improper operation.
Energy Recovery Wheel
See the “Energy Recovery Wheel” section.
Filters
Inspect the filters quarterly. Pressure drop readings can be used to determine when a filter should be replaced. Pre-filters should be replaced
according to the following chart or as required by system design.
All filter sections can be accessed by a door. Filters can be removed by sliding them out of the rack. Some filters are secured to the frame
using a clip. Aluminum filters can be removed and cleaned using high-pressure water