Control Variable
Default
Min.
Max.
Notes
Advanced Set-points, continued.
Temp Reset PID Tuning P Gain
6.000
0.001
999.999
Temp Reset PID I Time
300 sec.
0 sec.
1800 sec.
Temp Reset PID Cycle Time
30 sec.
0 sec.
100 sec.
Cooling/HP PID Tuning P Gain
3.000
0.001
999.999
Cooling/HP PID Tuning I Time
60 sec.
0 sec.
1800 sec.
Cooling/HP PID Tuning Cycle Time
1 sec.
0 sec.
100 sec.
Cooling/HP PID Tuning Deadband
0.0
0.0
10.0
Heating PID Tuning P Gain
3.000
0.001
999.999
Heating PID Tuning I Time
150 sec.
0 sec.
1800 sec.
Heating PID Tuning Cycle Time
1 sec.
0 sec.
100 sec.
Heating PID Tuning Deadband
0.0
0.0
10.0
Supply Duct Static PID P Gain
4.000
0.001
999.999
Supply Duct Static PID I Time
30 sec.
0 sec.
1800 sec.
Supply Space Static PI P Gain
100.000
0.001
999.999
Supply Space Static I Time
30 sec.
0 sec.
1800 sec.
Return Static PID P Gain
0.500
0.001
999.999
Return Static PID I Time
60 sec.
0 sec.
1800 sec.
Winter Ramp PID Tuning P Gain
1.000
0.001
999.999
Winter Ramp PID Tuning I Time
200 sec.
0 sec.
1800 sec.
Winter Ramp PID Tuning Cycle Time
1 sec.
0 sec.
100 sec.
Winter Ramp PID Tuning Deadband
1.0°F
0.0°F
50.0°F
OAD Airflow Ramp P Gain
0.015
0.001
999.999
OAD Airflow Ramp I Time
30 sec.
0 sec.
1800 sec.
Min OAD Airflow Ramp P Gain
0.020
0.001
999.999
Min OAD Airflow Ramp I Time
250 sec.
0 sec.
1800 sec.
Heat Wheel Bypass P Gain
2.000
0.001
999.999
Heat Wheel Bypass I Time
60 sec.
0 sec.
1800 sec.
Circuit Pressure P Gain
1.800
0.001
999.999
Circuit Pressure I Time
20 sec.
0 sec.
1800 sec.
Economizer P Gain
2.000
0.001
999.999
Economizer I Time
300 sec.
0 sec.
1800 sec.
Economizer Disable Fallback
Disabled (□)
Disabled (□)
Enabled (X)
Hot Gas Reheat P Gain
10.000
0.001
999.999
Hot Gas Reheat I Time
150 sec.
0 sec.
1800 sec.
CO
2
Control P Gain
4.000
0.001
999.999
CO
2
Control I Time
600 sec.
0 sec.
1800 sec.
Supply Fan Airflow P Gain
0.006
0.001
999.999
Supply Fan Airflow I Time
40 sec.
0 sec.
1800 sec.
Exhaust Fan Airflow P Gain
0.006
0.001
999.999
Exhaust Fan Airflow I Time
40 sec.
0 sec.
1800 sec.
HGRH Purge Mode Purge Interval
60 min.
30 min.
480 min.
HGRH Purge Mode Purge Duration
120 sec.
45 sec.
300 sec.
Login Duration
30 min.
5 min.
60 min.
Chilled Water Valve Position
Closed
Closed
Open
Modulating Compressor Minimum Signal
Cooling
12%
12%
100%
Modulating Compressor Minimum Signal
Dehumidify
50%
Cooling Min.
100%
Comp Signal Ramp Rate
30 sec.
1 sec.
100 sec.
Password Management - Service Password
9998
0001
9999
WSHP Freeze Protection
0.0°F
32.0°F
32.0°F
WSHP Compressor Delay
60 sec.
30 sec.
120 sec.