Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Control Variable
Default
Min.
Max.
Notes
Dehumidification Mode
Inside RH >
60%
0%
100%
Inside Dewpoint >
60.0°F
0.0°F
90.0°F
Outside Dewpoint >
60.0°F
0.0°F
100.0°F
Unoccupied Dehumidification Mode
Inside RH >
5%
0%
100%
Unoccupied Inside
Dewpoint >
70.0°F
0.0°F
90.0°F
Dehumidification Hysteresis
Humidity
4%
0%
10%
Dewpoint
2.0 Δ°F
0.0 Δ°F
10.0 Δ°F
Cold Coil Set-point
55.0°F
46.0°F
80.0°F
Priority Selection
Dehum. →Temp.
Disabled (□)
Disabled (□)
Enabled (X)
Disabled = Dehumidification Priority;
Enabled = Temperature Priority
Heat → Dehum.
Enabled (□)
Disabled (□)
Enabled (X)
Disabled = Heating Priority;
Enabled = Dehumidification Priority
Overcool Coil Offset
0.0 Δ°F
0.0 Δ°F
10.0 Δ°F
Dehumidification Force Comp. On
Clg Ramp 1
Enabled (X)
Disabled (□)
Enabled (X)
Table 31:
Dehumidification Control Set-Points Data Table.
Set-point availability varies based on unit configuration.
Table 32: Refrigeration Compressor Control Set-Points Data Table.
Control Variable
Default
Min.
Max.
Notes
Add Deadband
0.5 Δ°F
0.0 Δ°F
20.0 Δ°F
Sub Deadband
0.5 Δ°F
0.0 Δ°F
20.0 Δ°F
Cooling Delays
Interstage
60 sec.
10 sec.
600 sec.
Subtract
60 sec.
10 sec.
600 sec.
Heating Delays
Interstage
60 sec.
10 sec.
600 sec.
Subtract
60 sec.
10 sec.
600 sec.
Re-Add Delay
300 sec.
10 sec.
600 sec.
Min. On
60 sec.
1 sec.
600 sec.
Min. Off
270 sec.
1 sec.
600 sec.
Cold Coil Low Limit Set-
point
42.0°F
35.0°F
55.0°F
Coil Staging Safety Set-
point
46.0°F
35.0°F
55.0°F
CONTROLLER
Set-Points Data Tables