BACnet and MODBUS Points
Variable
Description
Active
Text
Inactive
Text
BACnet
MODBUS
Object
Instance
Object
Type
Access
Hyst Index Register
Type Size
Analog Inputs – Read Only
Cold_Coil_1_Temp_Analog_
Input
Cold Coil 1 Temperature
25
AI
ReadCOV_NoWrite 0.1 30244
Input
2
Exhaust_Temp_Analog_Input Exhaust Temperature
30
AI
ReadCOV_NoWrite 0.1 30254
Input
2
CL_Coil_Spt_Temp
Controls Lite Cooling
Coil Set-point
Temperature
31
AI
ReadCOV_NoWrite 0.1 30256
Input
2
CL_Supply_Spt_Temp
Controls Lite Supply Set-
point Temperature
32
AI
ReadCOV_NoWrite 0.1 30258
Input
2
Mixed_Temp_Analog_Input
Mixed Temperature
35
AI
ReadCOV_NoWrite 0.1 30264
Input
2
Outside_Air_Temp_Analog_
Input
Outside Air Temperature
37
AI
ReadCOV_NoWrite 0.1 30268
Input
2
Return_Temp_Analog_Input
Return Temperature
41
AI
ReadCOV_NoWrite 0.1 30276
Input
2
Leaving_Water_Temp_1_
Analog_Input
Leaving Water
Temperature Circuit A
42
AI
ReadCOV_NoWrite 0.1 30278
Input
2
Space_Setpoint_Slider_
Analog_Input
Space Set-point Slider
Analog Input
43
AI
ReadCOV_NoWrite 0.1 30280
Input
2
Space_Temp_Analog_Input
Space Temperature
44
AI
ReadCOV_NoWrite 0.1 30282
Input
2
Supply_Temp_Analog_Input
Supply Temperature
45
AI
ReadCOV_NoWrite 0.1 30284
Input
2
Entering_Water_Temp_1_
Analog_Input
Entering Water
Temperature Circuit A
46
AI
ReadCOV_NoWrite 0.1 30286
Input
2
Outside_RH_Analog_Input
Outside % Relative
Humidity
86
AI
ReadCOV_NoWrite 0.1 30350
Input
2
Return_RH_Analog_Input
Return % Relative
Humidity
88
AI
ReadCOV_NoWrite 0.1 30354
Input
2
Space_RH_Analog_Input
Space % Relative
Humidity
89
AI
ReadCOV_NoWrite 0.1 30356
Input
2
Space_Static_Pressure_
Analog_Input
Space Static Pressure
94
AI
ReadCOV_NoWrite 0.001 30366
Input
2
Supply_Duct_Static_
Pressure_Analog_ Input
Supply Duct Static
Pressure
95
AI
ReadCOV_NoWrite 0.01 30368
Input
2
Space_CO2_1_Analog_Input
Space 1 CO
2
ppm
116
AI
ReadCOV_NoWrite 10 30402
Input
2
Circuit_A_Discharge_
Pressure_Analog_ Input
Circuit A Discharge
Pressure
119
AI
ReadCOV_NoWrite 0.1 30408
Input
2
Circuit_B_Discharge_
Pressure_Analog_ Input
Circuit B Discharge
Pressure
121
AI
ReadCOV_NoWrite 1
30412
Input
2
Exhaust_Fan_Speed_
Analog_Input
Exhaust Fan Speed
Remote Command
Analog Input value
143
AI
ReadCOV_NoWrite 1
30456
Input
2
Supply_Fan_Speed_Analog_
Input
Supply Fan Speed
Remote Command
Analog Input value
155
AI
ReadCOV_NoWrite 1
30462
Input
2
Entering_Water_Temp_2_
Analog_Input
Entering Water
Temperature Circuit B
161
AI
ReadCOV_NoWrite 0.1 30468
Input
2
Leaving_Water_Temp_2_
Analog_Input
Leaving Water
Temperature Circuit B
162
AI
ReadCOV_NoWrite 0.1 30470
Input
2
Table 50:
BACnet and MODBUS Points List.
CONTROLLER
BACnet and MODBUS Points