80
Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 39: Advanced Set-Points Data Table.
Control Variable
Default
Min.
Max.
Notes
Login
Enter Password
0000
0000
9999
Current Access Level
Read Only
Read Only, Service Level, Factory Level
Manual Overrides
Manual Override Mode Enable
Disabled (X)
Disabled (□)
Enabled (X)
Manual Override Mode Duration
480 min.
0 min.
480 min.
Occupancy Override
Auto
Auto
Manual
Occupancy Value
Current
Operation
Unoccupied
Occupied
Supply Fan (1-4) Override
Auto
Auto
Manual
Supply Fan (1-4) Command (1-4)
Current
Command
Off
On
Supply Fan (1-4) Speed
Current Speed
0%
100%
Exhaust Fan (1-4) Override
Auto
Auto
Manual
Exhaust Fan Command (1-4)
Current Command
Off
On
Exhaust Fan Speed
Current Speed
0%
100%
Outside Damper Override
Auto
Auto
Manual
Outside Damper Position
Current Speed
0%
100%
Exhaust Damper Override
Auto
Auto
Manual
Exhaust Damper Position
Current Position
0%
100%
Compressor Request Override
Auto
Auto
Manual
Compressor Request Comp #: (1-8)
Current Request
Off
On
Compressor Signal Override
Auto
Auto
Manual
Compressor Signal Comp #: (1-8)
Current Signal
0%
100%
Cooling Ramp 1-4 Override
Auto
Auto
Manual
Cooling Ramp 1-4 Demand
Current Ramp %
0%
100%
Furnace Request Override
Auto
Auto
Manual
Furnace Request Furnace Stage (F1-8 S1-2)
Current State
Off
On
Electric Heat Override
Auto
Auto
Manual
Electric Heat Elec Heater #: (1-2)
Current Ramp %
0%
100%
Heating Ramp Override
Auto
Auto
Manual
Heating Ramp Demand
Current Ramp %
0%
100%
Heat Pump Heating Ramp Override
Auto
Auto
Manual
Heat Pump Heating Ramp Demand
Current Ramp %
0%
100%
Economizer Ramp Override
Auto
Auto
Manual
Economizer Ramp Value
Current Ramp %
0%
100%
Hot Gas Reheat Ramp Override
Auto
Auto
Manual
Hot Gas Reheat Ramp Value
Current Ramp %
0%
100%
Defrost Ramp Override
Auto
Auto
Manual
Reduces Energy Recovery -
100%= Full Bypass/Min Speed
Defrost Ramp Value
Current Ramp %
0%
100%
Energy Recovery Ramp Override
Auto
Auto
Manual
Energy Recovery Ramp Value
%
0%
100%
Pressure Control Override
Auto
Auto
Manual
Compressor Operation must be
off to override Pressure Control
Pressure Control Ramp No.: (1-8)
Current Ramp %
0%
100%
Pressure Control Override
Auto
Auto
Manual
Compressor Operation must be
off to override Pressure Control
Pressure Control AHPC VFD %
Current Ramp %
0%
100%
Pressure Control Fixed Stage No.: (2-4)
Current State
Off
On
Set-point availability varies based on unit configuration.
CONTROLLER
Set-Points Data Tables