101
Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Variable
Description
Active
Text
Inactive
Text
BACnet
MODBUS
Object
Instance
Object
Type
Access
Hyst Index Register
Type Size
Binary Values – Read Only, continued.
Al_DscgHiP_COMP.Active
Compressor Envelope
- High Discharge
Pressure Alarm
Alarm Normal
591
BV
ReadCOV_NoWrite 0
10541 Discrete
Al_DscgHiTemp_COMP.Active
Compressor Envelope
- High Discharge
Temperature Alarm
Alarm Normal
592
BV
ReadCOV_NoWrite 0
10542 Discrete
Al_DscgLowP_COMP.Active
EVD Low Discharge
Pressure Alarm
Alarm Normal
593
BV
ReadCOV_NoWrite 0
10543 Discrete
Al_EEPROM_EVD_1.Active
EVD EEPROM Alarm
Alarm Normal
594
BV
ReadCOV_NoWrite 0
10544 Discrete
Al_EEV_A_EVD_1.Active
ExV Motor Alarm -
Valve A
Alarm Normal
595
BV
ReadCOV_NoWrite 0
10545 Discrete
Al_EmergencyClosing_EVD_1.
Active
EVD Emergency
Closing Alarm
Alarm Normal
597
BV
ReadCOV_NoWrite 0
10547 Discrete
Al_EVD_Offline_EVD_1.Active
EVD Offline
Communication Alarm Alarm Normal
598
BV
ReadCOV_NoWrite 0
10548 Discrete
Al_FW_CompatibErr_EVD_1.
Active
EVD Firmware
Compatibility Alarm Alarm Normal
599
BV
ReadCOV_NoWrite 0
10549 Discrete
Al_HiCurr_COMP.Active
Compressor Envelope
- High Current Alarm Alarm Normal
600
BV
ReadCOV_NoWrite 0
10550 Discrete
Al_HiRatioP_COMP.Active
Compressor Envelope
- High Pressure Ratio
Alarm
Alarm Normal
601
BV
ReadCOV_NoWrite 0
10551 Discrete
Al_HiT_Cond_EVD_1.Active Al_HiT_Cond_EVD_1 Alarm Normal
602
BV
ReadCOV_NoWrite 0
10552 Discrete
Al_IncompleteClosing_EVD_1.
Active
EVD Incomplete
Closing Alarm
Alarm Normal
603
BV
ReadCOV_NoWrite 0
10553 Discrete
Al_LOP_A_EVD_1.Active
EVD Low Operating
Pressure Alarm - Valve A Alarm Normal
604
BV
ReadCOV_NoWrite 0
10554 Discrete
Al_Low_SH_A_EVD_1.Active
"EVD Low SuperHeat
Alarm
- Circuit A"
Alarm Normal
606
BV
ReadCOV_NoWrite 0
10556 Discrete
Al_LowDeltaP_COMP.Active
Compressor Envelope
- Low Pressure
DeltaAlarm
Alarm Normal
608
BV
ReadCOV_NoWrite 0
10558 Discrete
Al_LowRatioP_COMP.Active
Compressor Envelope
- Low Pressure Ratio
Alarm
Alarm Normal
609
BV
ReadCOV_NoWrite 0
10559 Discrete
Al_LowSuct_A_EVD_1.Active
Low Suction
Refrigerant
Temperature - Circuit A
Alarm Normal
610
BV
ReadCOV_NoWrite 0
10560 Discrete
Al_MOP_A_EVD_1.Active
EVD Max Operating
Pressure Alarm - Valve A Alarm Normal
612
BV
ReadCOV_NoWrite 0
10662 Discrete
Al_S1_EVD_1.Active
EVD-S1 Suction
Pressure Sensor Alarm Alarm Normal
614
BV
ReadCOV_NoWrite 0
10564 Discrete
Al_S2_EVD_1.Active
EVD-S2 Suction
Temperature Sensor
Alarm
Alarm Normal
615
BV
ReadCOV_NoWrite 0
10565 Discrete
Al_S4_EVD_1.Active
EVD-S4 Discharge
Temperature
Sensor Alarm
Alarm Normal
617
BV
ReadCOV_NoWrite 0
10567 Discrete
Table 60:
BACnet and MODBUS Points List, continued.
CONTROLLER
BACnet and MODBUS Points