20. Quick Reference Guide - Error Codes
Table 6. Single-Zone 009/012 115VAC/208-230VAC
LED Display (LED 1: Blue)
Error Description
Slow Flash
Standby
On
Normal operation
Fast Flash
Outdoor unit error.
Slow flash -- flashing at 1Hz.
Fast flash - flashing at 2Hz.
Table 7. Single-Zone 018/030 208-230VAC
Main Control
IPM Control (comp. driver)
Error Description
Blue LED
Red LED
Green LED
Slow Flash
OFF
ON
Stand-by
ON
ON
OFF
Normal operation
Fast Flash
OFF
ON
Could be one of the following:
•
Indoor and outdoor unit communication error.
•
Outdoor unit temperature sensor error.
•
Outdoor unit EEPROM error
•
Compressor top temperature switch is open.
Fast Flash
ON
ON
DC bus voltage is too high or to low protection.
Fast Flash
Fast Flash
ON
Driver EEPROM error.
Fast Flash
Fast Flash
OFF
Driver chip start-up failure.
Fast Flash
ON
Fast Flash
Could be one of the following:
•
Driver phase loss protection
•
Driver zero speed protection
•
PWM synchronization failure.
Fast Flash
OFF
Fast Flash
IGBT over-current or IPM over-current
Fast Flash
Fast Flash
Fast Flash
Control chip communication error.
Slow flash - Flashing at 1Hz
Fast flash- Flashing at 2Hz
Table 8. Multi-Zone Outdoor Unit
Display
Error Description
E0
Outdoor unit EEPROM error.
E2
Communication error between outdoor unit and all indoor units.
E3
Communication error between outdoor unit main control and IPM control.
E4
Temperature sensor error (outdoor coil, outdoor ambient , compressor discharge and indoor unit coil outlet temperature sensors.
E5
High and low voltage protection.
E8
Outdoor DC fan speed error.
F1
Indoor unit #1 coil outlet temperature sensor error.
F2
Indoor unit #2 coil outlet temperature sensor error.
F3
Indoor unit #3 coil outlet temperature sensor error.
F4
Indoor unit #4 coil outlet temperature sensor error.
F5
Indoor unit #5 coil outlet temperature sensor error.
F6
Indoor unit #6 coil outlet temperature sensor error.
P1
High pressure switch open
P2
Low pressure switch open
P3
Outdoor compressor current overload sensed.
P4
High temperature sensed at compressor discharge line.
P5
High temperature sensed at outdoor coil.
P6
Inverter module (IPM) error.
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...