121
Error Code:
P3
Description:
Outdoor compressor current overload sensed
General Note:
If the outdoor current exceeds the current limit value, the LED will display the failure.
Current protection of compressor.
Check whether the input current of the power
supply should not exceed more than 12A for 18K BTU
units.
For 30K, 18.5A.
For 36K, it is 23A.
Yes
Check whether the refrigerant system is OK.
Check whether the outdoor ambient temperature
is higher than 50°C or 122 F
No
Replace outdoor main board.
No
Stop the unit.
Yes
Check if outdoor unit has proper ventilation.
No
Correct poor ventilation to outdoor unit.
Yes
Check outdoor coils. Outdoor coils should be clean
and free of any debris.
Clean outdoor coils.
Yes
No
Judge 5: The refrigerant pipe is blocked.
Recover refrigerant and remove restriction(s).
Perform proper vacuum procedures, then
restart system.
Yes
No
Replace outdoor main board, and check whether the
system can run normally.
No
Replace the electric control box.
Problem Solved.
Yes
Yes
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...