93
Table 3. Status Indicators
Display
Remark
47
Indoor unit F capacity demand code
Not used
48
Indoor unit F evaporator outlet temp.(T2BF)
Not used
49
Indoor unit F room temp.(T1F)
Not used
50
Indoor unit F evaporator temp.(T2F)
Not used
51
EXV open angle for F indoor unit
Not used
19.4. Outdoor Unit Digital Display Tube
There is a digital display tube in outdoor PCB. Digital display tube display function
Table 4. Operation Display
Description
In standby , the LED displays “- -”
In compressor operation, the LED display the running frequency,
In defrosting mode, The LED displays “dF” or alternative displays between running frequency and “dF”(each displays 0.5s)
In compressor pre-heating, The LED displays “PH” or alternative displays between running frequency and “PH”(each displays 0.5s)
During the oil return process, The LED displays “RO” or alternative displays between running frequency and “RO”(each displays 0.5s)
In low ambient cooling mode, the LED displays “LC” or alternative displays between running frequency and “LC”(each displays 0.5s)
In forced cooling mode, the LED displays “FC” or alternative displays between running frequency and “FC”(each displays 0.5s)
When PFC module protection occurs three times within 15 minutes, the LED displays “E6” or alternative displays between running frequency and
“E6”(each displays 0.5s)
In protection or malfunction, the LED displays error code or protection code.
19.5. Dry Mode Operation - MWMA and MWMB
19.5.1. Procedure
1.
Press the
MODE
button to select
DRY
mode.
2.
Press the
UP/ DOWN
button to select the desired temperature. The temperature setting range is from 62°F to 86°F in
one degree increments.
NOTE:
The blower is preset at a low speed and cannot be changed therefore it will get cold and most likely will over
shoot the temperature setting by 6-10 degrees depending on the room size or other various factors. Also the
Follow Me
mode does not operate in this mode.
The Follow Me
mode is only available when a return air sensor
is utilized. Typically in most cases the
Follow Me
mode will not be sufficient to remove excessive humidity.
In addition, the outdoor units do not have a humidistat installed therefore they are unable to determine humidity
levels. This product is not recommend as a main source for dehumidification.
19.5.2. Dry Mode Operation Sequence
When in dry mode operation the unit is actually in cooling mode with a low speed blower operation. The compressor will stop
when the room temperature is two degrees Celsius lower than the temperature setting.
However there is a temperature compensation for cooling mode that is two degrees Celsius. So the unit will stop when the
temperature is four degrees Celsius lower than the room temperature settings.
NOTE:
Four degrees Celsius is equivalent to 8°F difference.
19.6. Test Run - MWDA and MWMB
Only perform test run after you have completed the following steps:
•
Electrical Safety Checks – Confirm that the unit’s electrical system is safe and operating properly
•
Gas Leak Checks – Check all flare nut connections and confirm that the system is not leaking
•
Confirm that gas and liquid (high and low pressure) valves are fully open.
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...