117
Error Code:
P1
Description:
High pressure switch open.
General Note:
If the sampling voltage is not 5V, the LED will display the failure.
High Pressure Protection
Check wiring connections between high pres
-
sure switch and main PCB.
Yes
Determine if High pressure switch is faulty.
Method: Disconnect the plug. Measure the
resistance of the high pressure protector, if the
protector is normal the value is 0.
Yes
Make necessary corrections.
No
Replace high pressure protection
switch.
No
Check the outdoor ambient temperature. The
outdoor ambient temperature should not be
higher than 50 °C or 122 °F.
No
Stop the unit.
Yes
Check if the outdoor unit ventilation is good
Yes
Make corrections to allow for proper
ventilation
No
Check if the outdoor fan runs properly
See Error code E8 to properly diag-
nose outdoor fan motor.
No
Yes
Check outdoor coils. The outdoor unit coils
should be clean and free of any debris.
Clean outdoor coils.
Yes
No
Replace outdoor main board.
No
Check whether the refrigerant system is OK.
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...