92
Table 3. Status Indicators
Display
Remark
8
Indoor unit A capacity demand code
Norm code*HP
(9K:1HP,12K:1.2HP,18K:1.5HP)
9
Indoor unit B capacity demand code
10
Indoor unit C capacity demand code
11
Indoor unit D capacity demand code
12
Indoor unit E capacity demand code
13
Outdoor unit amendatory capacity demand code
Forced cooling:7
14
The frequency corresponding to the total indoor
units amendatory capacity demand
15
The frequency after the frequency limit
16
The frequency sending to compressor control chip
17
Indoor unit A evaporator outlet temp.(T2BA)
If the temp. is lower than -9 degree, the digital display tube will show “-9”.If the temp.
is higher than 70 degree, the digital display tube will show “70”. If the indoor unit is not
connected, the digital display tube will show: “――”
18
Indoor unit B evaporator outlet temp.(T2BB)
19
Indoor unit C evaporator outlet temp.(T2BC)
20
Indoor unit D evaporator outlet temp.(T2BD)
21
Indoor unit E evaporator outlet temp.(T2BE)
22
Indoor unit A room temp.(T1A)
If the temp. is lower than 0 degree, the digital display tube will show “0”.If the temp. is
higher than 50 degree, the digital display tube will show “50”. If the indoor unit is not
connected, the digital display tube will show: “――”
23
Indoor unit B room temp.(T1B)
24
Indoor unit C room temp.(T1C)
25
Indoor unit D room temp.(T1D)
26
Indoor unit E room temp.(T1E)
27
Indoor unit A evaporator temp.(T2A)
If the temp. is lower than -9 degree, the digital display tube will show “-9”.If the temp.
is higher than 70 degree, the digital display tube will show “70”. If the indoor unit is not
connected, the digital display tube will show: “――”
28
Indoor unit B evaporator temp.(T2B)
29
Indoor unit C evaporator temp.(T2C)
30
Indoor unit D evaporator temp.(T2D)
31
Indoor unit E evaporator temp.(T2E)
32
Condenser pipe temp.(T3)
33
Outdoor ambient temp.(T4)
34
Compressor discharge temp.(TP)
The display value is between 30~129 degree. If the temp. is lower than 30 degree, the
digital display tube will show “30”.If the temp. is higher than 99 degree, the digital display
tube will show single digit and tens digit. For example, the digital display tube show “0.5”,it
means the compressor discharge temp. is 105 degree.)
35
AD value of current
The display value is hex number.
For example ,the digital display tube show “Cd”, it means AD value is 205.
36
AD value of voltage
37
EXV open angle for indoor unit A
Actual data/4.
If the value is higher than 99, the digital display tube will show single digit and tens digit.
For example ,the digital display tube show “2.0”,it means the EXV open angle is
120×4=480p.)
38
EXV open angle for indoor unit B
39
EXV open angle for indoor unit C
40
EXV open angle for indoor unit D
41
EXV open angle for indoor unit E
42
Frequency limit symbol
Bit7
Frequency limit caused by IGBT radiator
The display value is hex number.
For example, the digital display
tube shows 2A,then Bit5=1,
Bit3=1, Bit1=1.
It means frequency limit caused
by T4, T3 and current.
Bit6
Frequency limit caused by PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
Bit2
Frequency limit caused by T5.
Bit1
Frequency limit caused by current
Bit0
Frequency limit caused by voltage
43
Average value of T2
(Sum T2 value of all indoor units)/( number of indoor units in good connection)
44
Outdoor unit fan motor state
Off:0, High speed:1, Med speed:2, Low speed:3 Breeze:4, Super breeze:5
45
The last error or protection code
00 means no malfunction and protection
46
Indoor unit F capacity
Not used
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...