90
19. Start-Up
19.1. Adding Refrigerant - Single-Zone Systems
The outdoor unit is factory-charged with refrigerant. Calculate the additional refrigerant required according to the diameter
and the length of the liquid pipe between the outdoor unit and indoor unit connections.
Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
NOTE:
Interconnecting pipe work between outdoor and indoor units must be 10 ft. or longer.
NOTE:
Do not remove refrigerant for line lengths less than 25 ft. R-410A is a blended refrigerant. If you must remove
charge, it is necessary to remove the entire charge and weigh in the new charge.
Table 1. Adding Refrigerant
System Size (KBtu)
Pipe Length
Amount of Refrigerant to add
09
>25 ft. (7.5m)
0.161 oz/ft (15g/m)
12
>25 ft. (7.5m)
0.161 oz/ft (15g/m)
18
>25 ft. (7.5m)
0.161 oz/ft (15g/m)
24
>25 ft. (7.5m)
0.322 oz/ft (30g/m)
36
>25 ft. (7.5m)
0.322 oz/ft (30g/m)
48
>25 ft. (7.5m)
0.322 oz/ft (30g/m)
19.2. Adding Refrigerant - Multi-Zone Systems
The outdoor unit is factory-charged with refrigerant. Calculate the additional refrigerant required according to the length of
the liquid pipe (one way) between the outdoor unit and indoor unit connections.
Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
NOTE:
Interconnecting pipe work between outdoor and indoor units must be 10 ft. or longer.
NOTE:
Do not remove refrigerant for line lengths less than 25 ft. R-410A is a blended refrigerant. If you must remove
charge, it is necessary to remove the entire charge and weigh in the new charge.
Table 2. Adding Refrigerant
System
Pre-charge
Pipe Length
Amount of Refrigerant to add
Two-port
50 ft. (15 m)
0.16 oz ((L1 ft + L2 ft) - 50 ft)
0.005 kg ((L1 m + L2 m) - 15 m)
Three-port
75 ft. (23 m)
0.16 oz ((L1 ft + L2 ft + L3 ft) - 75 ft)
0.005 kg ((L1 m + L2 m + L3 m) - 23 m)
Four-port
100 ft. (30 m)
0.16 oz ((L1 ft + L2 ft + L3 ft + L4 ft) - 100 ft)
0.005 kg ((L1 m + L2 m + L3 m + L4 m) - 30 m)
Five-port
125 ft. (38 m)
0.16 oz ((L1 ft + L2 ft + L3 ft + L4 ft + L5 ft) - 125 ft)
0.005 kg ((L1 m + L2 m + L3 m + L4 m + L5 m) - 38 m)
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...