9
1.5.
MPB Single-Zone Specifications Outdoor Units (2 - 4 Ton)
Nominal Size - Tons
2
2.5
3
4
Outdoor Unit Model No.
MPB024S4S
MPB030S4S
MPB036S4S
MPB048S4S
Ambient Temperature Operating
Range - °F
Cooling
–13 - 122
–13 - 122
–13 - 122
–13 - 122
Heating
–13 - 86
–13 - 86
–13 - 86
–13 - 86
Energy Star
Yes
No
No
No
Sound Data (dBA)
Cooling/Heating
61
59
66
62.5
Refrigerant
(R-410A)
Charge furnished
5 lbs. 3 oz.
5 lbs. 11 oz.
6 lbs. 12 oz.
9 lbs. 4 oz.
Maximum line length with furnished charge - ft.
25
25
25
25
Additional charge required per ft. - oz.
0.32
0.32
0.32
0.32
Compressor
No. and Type
(1) Rotary
(1) Rotary
Twin-Rotary
Twin-Rotary
Refrigerant oil type
POE Oil
VG74
POE Oil
VG74
POE Oil
VG74
Ester Oil
VG74
Refrigerant oil charge - oz.
22.7
22.7
33.8
47.3
Low ambient cut-off
–13°F
5°F
5°F
5°F
Connections - in.
Liquid/Gas pipe (flare)
3/8 / 5/8
3/8 / 5/8
3/8 / 5/8
3/8 / 5/8
Maximum refrigerant pipe length - ft.
164
164
213
213
Max. difference in level of indoor unit - ft.
82
82
98
98
Outdoor
Fan(s)
(No.) Diameter - in.
(1) 20
(1) 20
(1) 20
(2) 22
Total air volume - cfm
2235
2130
2530
4470
rpm
810/700/500
810/700/500
950
(2) 900
Outdoor Coil
Number of rows
2.6
2.6
2
2
Fins per inch
18
18
19
18
Fin type
Hydrophilic aluminium
Tube outside diameter - in.
5/16
5/16
3/8
3/8
Tube type
Rifled copper tubing
Net face area - ft.
2
8.24
8.24
8.24
6.43 (inner coil) /
6.97 (outer coil)
Application area - sq. ft.
345 - 505
430 - 630
515 - 755
690 - 1010
Design Pressure
PSIG
550/340
550/340
550/340
550/340
Shipping
Data
Net/Shipping weight (lbs.)
137 / 149
149 / 161
149 / 161
218 / 246
ELECTRICAL DATA
Electrical Characteristics - 60 Hz - 1 Phase
208/230V
208/230V
208/230V
208/230V
1
Maximum Overcurrent Protection (amps)
25
30
50
50
2
Minimum circuit ampacity
18
20
30
35
Compressor Rated load amps
12
15
22
23.5
Outdoor Fan Motor
Rated load amps
0.6
0.6
1.0
(2) 0.39
Output - W
120
120
120
(2) 85
NOTE - Extremes of operating range are plus and minus 10% of line voltage.
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...