134
Error Code:
EC
Description:
Low Refrigerant Error
General Note:
The system monitors the value of evaporator coil sensor T2 for the first 5 minutes after startup. If the temperature of T2
drops per this formula three times in the first 5 minutes of operation, the system shuts down and the error code displays.
For this formula “Tcool” = the T2 temperature at startup.
T2 < Tcool - 3.6°F (2°C)
EC
Power off then restart the unit in 2 min
-
utes.
Yes
Yes
Check the T2 sensor. Is
it functioning
Check to see if cool air is blowing out of
the indoor air outlet
No
Yes
Replace the indoor PCB
Check for refrigerant leaks.
No
Yes
Repair leaks and re
-
charge system.
Check for restriction in refrigerant lines.
Clear restriction.