109
Error Code:
E5
Description:
High or low voltage protection
General Note:
An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.
Voltage protection
Check the voltage of outdoor unit power
supply, the voltage between
L1 and L2 range min. 187~ 253VAC max.
Yes
Check whether the voltage of IPM board
P and N is normal? 277-356VDC for
18-30KBtu/h; 277-410VDC for 36KBtu/h.
No
Replace bridge rectifiers, and then check
whether the system operates normally.
(Only for 4-zone MPA036 & MLA036
units)
No
Replace IPM board, and then check
for normal unit operation.
No
Replace outdoor main board.
Problem Solved.
Yes
Yes
Check the primary power supply.
No
Содержание MWMA009S4-*L