142
Error Code:
F6
Description:
Indoor Unit Evaporator Outlet Coil Temperature Sensor Faulty
General Note:
If the voltage is lower than 0.06V or higher than 4.94V, the LED will display the error.
Temperature sensor error
Check the connections between tempera
-
ture sensor and PCB. Are the connec
-
tions good?
Yes
No
No
Correct the connections
Check the resistance value of the sensor
via Appendix 1 and Appendix 2.
Yes
Replace indoor or out
-
door PCB.
Is it normal?
No
Replace the sensor.