Error Code:
E2 (continued)
Use a multimeter to test the DC voltage between 2 port and
3 port of outdoor unit. The red pin of multimeter connects
with 2 port while the black pin is for 3 port.
When unit is normal running, the voltage will move alternately
between positive value and negative value.
Self-Check OK
Power (some
modles)
Opera ng
Power (some
models)
IPM (for 2-zone/3-zone)
Main board LED when power on and unit
standby.