Error Code:
P6 (continued)
Low Pressure Connection
Is the wiring between the low pressure switch and
main control board is connected properly.
Yes
Is the low pressure protector broken?
Method: Disconnect the plug. Measure the resistance
of the low pressure protector, if the protector is normal
the value is 0.
Yes
Connect it properly..
No
Replace low pressure protector.
No
Check whether the outdoor ambient temperature is to
low.
No
Stop the unit.
Yes
Check whether the high pressure valve is opened.
Yes
Fully open the high pressure valve.
No
Check if the indoor fan runs properly in cooling mode.
Refer to the solution of fan speed mal
-
function (E8). Find out the cause correct
it.
No
Yes
Replace outdoor main board.
No
Refrigerant is not enough. Add the refrigerant.
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...