106
Error Code:
E3
Description:
Communication error between outdoor unit main control and IPM.
General Note:
PCB main chip does not receive feedback from IPM during 60 seconds.
Communication malfunction between IPM
board and outdoor main board.
Is there at least one LED in the IPM
board light?
No
Check the signal wire between the IPM
module and the main board, is it con
-
nected correctly?
No
Reconnect and retry. Does error still
display?
Yes
Replace IPM board, and then check
whether the system operates normally.
No
Replace outdoor main board, and then
check whether the system operates
normally.
No
Replace the electric control box.
Problem Solved.
Yes
Yes
No
Yes
Yes