7
1.3.
MPA Single-Zone Specifications Outdoor Units (2.0 - 4.0 Ton)
Nominal Size - Tons
2
2.5
3
4
Outdoor Unit Model No.
MPA024S4S
MPA030S4S
MPA036S4S
MPA048S4S
Ambient Temperature Operating
Range - °F
Cooling
5 - 122
5 - 122
5 - 122
5 - 122
Heating
–13 - 86
–13 - 86
–13 - 76
–13 - 76
Sound Data (dBA)
Cooling
59
59
62
63
Heating
63
61
65
65
Refrigerant
Charge furnished (R-410A)
5 lbs. 3 oz.
6 lbs. 10 oz.
7 lbs. 13 oz.
9 lbs. 8 oz.
Maximum line length with furnished charge - ft.
25
25
25
25
Additional charge required per ft. - oz.
0.32
0.32
0.32
0.32
Compressor
No. and Type
Twin-Rotary
Rotary
Twin-Rotary
Twin-Rotary
Refrigerant oil type
Ester Oil VG74
FY50S
FV50S
FV50S
Refrigerant oil charge - oz.
27.7
36.1
36.1
47.3
Low ambient cut-off
–13°F
–13°F
–13°F
–13°F
Connections - in.
Liquid/Gas pipe (flare)
3/8 / 5/8
3/8 / 5/8
3/8 / 5/8
3/8 / 5/8
Maximum refrigerant pipe length - ft.
164
164
213
213
Max. difference in level of indoor unit - ft.
82
82
98
98
Outdoor
Fan
(No.) Diameter - in.
(1) - 22
(1) - 22
(1) - 22
(2) - 20
Total air volume - cfm
2355
2530
2940
4240
rpm
850/750/700
950/800/750
950
860
Outdoor Coil
Number of rows
2.6
2.6
2.6
2
Fins per inch
18
16
14
16
Fin type
Hydrophilic aluminium
Tube outside diameter - in.
1/4
1/4
3/8
5/16
Tube type
Rifled copper tubing
Net face area - ft.
2
8.12
7.79 / 4.75
8.16 / 4.75
14.14
Design Pressure
PSIG
550/340
550/340
550/340
550/340
Shipping Data
Net/Shipping weight (lbs.)
134 / 144
158 / 170
161 / 183
220 / 251
ELECTRICAL DATA
Electrical Characteristics - 60 Hz - 1 Phase
208/230V
208/230V
208/230V
208/230V
1
Maximum Overcurrent Protection (amps)
25
30
50
50
2
Minimum circuit ampacity
18
20
30
35
Compressor Rated load amps
12
14
22
23.5
Outdoor Fan Motor
Rated load amps
0.7
1.0
1.0
(2) 0.7
Output - W
120
120
120
(2) 85
NOTE - Extremes of operating range are plus and minus 10% of line voltage.
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...