10
1.6.
MLA Single-Zone Specifications Outdoor Units (0.75 - 2 Ton)
Nominal Size - Tons
0.75
1
1.5
2
Outdoor Unit Model No.
MLA009S4S-1P
MLA012S4S-1P
MLA018S4S-1P
MLA024S4S-1P
Ambient Temperature Operating
Range - °F
Cooling
–22 - 122
–22 - 122
–22 - 122
–22 - 122
Heating
–22 - 86
–22 - 86
–22 - 86
–22 - 86
Sound Data (dBA)
Cooling
52
52
56
57
Heating
57
57
59
60
Refrigerant
Charge furnished (R-410A)
3 lbs. 3 oz.
3 lbs. 3 oz.
4 lbs. 3 oz.
5 lbs. 7 oz.
Maximum line length with furnished charge - ft.
25
25
25
25
Additional charge required per ft. - oz.
0.16
0.16
0.16
0.32
Compressor
No. and Type
Rotary
Rotary
Rotary
Rotary
Refrigerant oil type
Ester Oil VG74
Ester Oil VG74
POE VG74
POE VG74
Refrigerant oil charge - oz.
16.9
16.9
22.7
22.7
Low ambient cut-off
–30
–30
–30
–30
Connections - in.
Liquid/Gas pipe (flare)
1/4 / 3/8
1/4 / 1/2
1/4 / 1/2
3/8 / 5/8
Maximum refrigerant pipe length - ft.
82
82
98
164
Max. difference in level of indoor unit - ft.
33
33
66
82
Outdoor
Fan
(No.) Diameter - in.
(1) 17
(1) 17
(1) 19
(1) 22
Total air volume - cfm
1120
1180
1355
2355
rpm
810
810
850
810
Outdoor Coil
Number of rows
2
2
2
2
Fins per inch
18
18
18
19
Fin type
Hydrophilic aluminium
Tube outside diameter - in.
3/8
3/8
3/8
3/8
Tube type
Rifled copper tubing
Net face area - ft.
2
4.73
4.73
5.19
8.16
Design Pressure
PSIG
550/340
550/340
550/340
550/340
Shipping Data
Net/Shipping weight (lbs.)
88/94
88/94
108/115
136/149
ELECTRICAL DATA
Electrical Characteristics - 60 Hz - 1 Phase
208/230V
208/230V
208/230V
208/230V
1
Maximum Overcurrent Protection (amps)
15
15
25
30
2 Minimum circuit ampacity
9
9
18
20
Compressor Rated load amps
5.25
5.65
12.3
14
Outdoor Fan Motor
Rated load amps
0.38
0.38
0.42
0.5
Output - W
40
40
44
120
NOTE - Extremes of operating range are plus and minus 10% of line voltage.
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Содержание MWMA009S4-*L
Страница 105: ...105 Error Code E2 continued Check point button press 1 time to check how many indoor units are connected ...
Страница 110: ...110 Error Code E5 continued IPM for 4 zone P N for 2 zone and 3 zone IPM for 2 zone and 3 zone ...
Страница 111: ...111 Error Code E5 continued P N for 4 zone Bridge rectifier for 2 zone and 3 zone Bridge rectifier for 4 zone ...
Страница 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Страница 118: ...118 Error Code P1 continued ...
Страница 120: ...120 Error Code P2 continued ...
Страница 122: ...122 Error Code P3 continued ...
Страница 144: ...144 Error Code P0 continued P U P V ...
Страница 145: ...145 P W P N ...
Страница 151: ...151 Error Code P6 continued ...