50
Operating Manual
OMBG3000 – Iss.01
© Copyright 2016
Default Configuration of the BIOGAS 3000 Modbus Port
4.10.2
The BIOGAS 3000 Modbus port has a default configuration of the following:
Node Address
1
Baud Rate
19200
Parity
Even
Stop Bits
1
Termination
Off
The BIOGAS 3000 acts as a slave.
The protocol is MODBUS RTU.
Note: A termination resistor of 200 ohms is fitted internally between the
positive and negative Modbus signals of the BIOGAS 3000, which must be
the last connection on the ‘bus’. The termination resistor can be turned
‘On’ or ‘Off’ via the menu on the BIOGAS 3000 module (see
). Similarly, the master device on the ‘bus’ should have a
termination resistor.
Note: The node address, baud rate, parity, and termination are all
configurable settings found within the menu of the BIOGAS 3000 module;
see section
Readable Parameters of the BIOGAS 3000
4.10.3
Below is a table of addresses that can be read from the BIOGAS 3000.
Read-Only Single Bit Registers
Register
Address
(Dec) (Hex) Parameter
Content Information
0
0000h System status
0 – system OK
1 – system fault
1
0001h Flow status
0 – flow OK
1 – flow fail
2
0010h
Communications
status
0 – communications OK
1 – communications error
3
0011h Catchpot status
0 – catchpot empty
1 – catchpot full
Содержание BG3K2