46
Operating Manual
OMBG3000 – Iss.01
© Copyright 2016
possible so that it can be easily reached and clearly identified as the
disconnecting device for the system.
The mains cable must be three core cable (live, neutral and earth) and enter
the enclosure via a cable gland (see
Cable Gland Selection and Cord
) through the mains supply customer cable entry point (see
Figure 3 - BIOGAS 3000 customer connections
How to Wire the Mains Supply
4.9.2
Warning
Only a qualified person should make electrical
connections to the system.
Ensure the power is isolated and the
removed before wiring to the system.
Failure to connect a suitable earth to the system could
result in serious injury.
The equipment must be provided with a double-pole
switched and fused mains supply. The switch must be
mounted as close to the equipment as practicably
possible and clearly identified as the disconnecting
device for the system.
Cable glands should meet the requirements of
Gland Selection and Cord Anchorage
Cable insulation and conductor sizes must meet the
requirements of
Cable Conductor Sizes and Insulation
If using armored cable, the armor must not be used as
the main earth connection for the BIOGAS 3000. If
earthing of the armor is required, this must not be taken
from the BIOGAS 3000.
All cables should be crimped with an appropriate
insulated ferrule for the size of the cable being used. In
addition, the cable insulation must be housed
adequately within the protective sheath of the ferrule.