Draining the heating system
When it is necessary to drain the heating system, proceed
as described here below:
f
Connect a rubber pipe to the draining tap terminal
1
;
f
put the other end of the pipe in a suitable drain or sink;
f
open the draining tap by turning the nut
2
counter-
clockwise, using a suitable spanner;
f
when the pressure is COMPLETELY drained, it's possible
to open the radiators venting valves, to allow the air
inlet� The complete system drain is possible only drain
-
ing the liquid from the lowest point of the system itself.
Remark:
The complete system draining can be achieved only by drain-
ing the system from its lowest point.
f
when everything is over, close taps (turning the nut
2
clockwise) and
air vents�
In the primary exchanger a certain quantity of water of the heat-
ing system remains. If you want to remove the boiler from the
wall, we advice you to close with plugs the hydraulic inlet/outlet
heating system connections.
f
Drain the storage unit if necessary (storage tank and/or primary coil). Refer to the relevant docu-
mentation.
Pump settings
The pump has a selector which allows to reduce the
speed, so as to reduce the noise produced by the too
rapid circulation of the liquids in too small heating sys-
tems�
•
III
=
Maximum
Speed (Factory setting)
•
II
=
Medium
Speed
•
I = Minimum
Speed (use only if strictly necessary; test the heating system, verifying that no over-
heating problems occur).
Alarms - boiler block
Following a malfunction, the boiler can lockout and show a particular signal,
or
on
the display, with an alarm code
"E…"
. In the following table, all the alarm signals are listed, their most
probable causes and the suggested solutions. Generally:
•
identifies those
alarms the user can restore
by pressing the
button. It normally
blinks
, but after 5 reset actions in 24 hours the action on the
button has no more effect.
To have 5 further reset possibilities, it's possible to switch off the electrical supply to the boiler for 30 seconds, by using the
purposed external switch, even if this work-around won't solve the problem and it will be necessary to call the Service Centre;
•
identifies those
alarms the user can not restore
, as they are generated by the diag-
nostic system when a component has been detected as faulty.
The user is allowed to switch off the electri-
cal supply to the boiler for 30 seconds, by using the purposed external switch, but should the alarm happen again, it will be
necessary to call the Service Centre.