reinsert the connector
4
and check that MAX pressure is not changed;
Important:
LOCK THE ADjUSTMENT DEVICE AFTER ANY SETTING OPERATION.
• mount the cap
C
;
7.
screw the pressure tapping point screw for gas outlet
1
and
verify that there is no gas leak
�
8.
To switch the burner off, quit the technical menu (see "PCB parameters settings (technician menu)"
on page 27). The boiler returns to
mode�
PCB parameters settings (technician menu)
These settings are reserved to Technician only. The procedure how the get in the boiler parameters is
known by technician only thanks to a combination of steps which allows to gain the boiler parameters.
A few of these settings allow to optimise and tailor the boiler working, while a few others allow to set
the boiler during maintenance operation.
Once entered the Technician menu:
•
the 2-digits display
on the
left
side of the display indicates the number of
the parameter
, and you
can choose the parameter (among the ones available)
by rotating the knob
.
•
the 3-digits display
on the
right
side is referred to the
value (setting)
of the parameter, and you
can set it
by rotating the knob
�
In case of PCB replacing, check all of the parameter settings otherwise set them properly.
Please, do not modify any firm setting if this is not required.
Main boiler parameters (PC)
The parameters listed in the following table are limited to those described in this handbook� The com
-
plete parameter list is available in the documentation for the technician.
Param
-
eter
Adj. range
(fact. set.)
and values
Description
01
0; 1
(0)
Type of GAS supply
0
for
Natural Gas (G20)
supply
1
for
LPG (G30/G31)
supply
To change the type of gas supply, it is necessary to follow the complete instructions
described in the paragraph "Gas conversion" on page 31.
03
—
It indicates the CH boiler power during the soft ignition phase.
We recom-
mend to leave the factory setting unchanged.
04
0…99
(99)
We recommend to leave the factory setting unchanged.
05
0…2
(0)
Pump functioning mode during heating working
0
intermittent
for normal applications
(with eventual delay defined by parameter 06)
1
always on
(to fit the needs of particular plants)
2
always off
(use only when external pumps are foreseen).
Remark: The pump will be anyway activated in all other circumstances, e.g.
during the DHW
functioning or for anti-freezing or anti-lockout functions.