Gas connection
Due to various installation possibilities, the gas cock
3
supplied with the original Connections Kit has a
simple male Ø ½” connection, facing the rear of the boiler.
The gas pipe
4
, upstream the gas cock
3
, should
be supplied by the installer.
While connecting the gas inlet of the boiler to the gas supply piping, it is MANDATORY to
insert a PLAIN GASKET, whose dimensions and material must be adequate. Connection is NOT
suitable for hemp, teflon strip or similar materials. Because of the type of fitting, the use of
those materials does not make the suitable seal with consequent gas leaks!
This boiler is factory set to be supplied with Natural Gas G20 (Methane). It can be converted,
always by a qualified technician and using original spare parts, to operate with LPG (G30/G31)
�
Using LPG, it is absolutely necessary to install a pressure reducer upstream the boiler. Failure
to do this, the gas valve of the boiler will get damaged. The inlet gas pressure must be compli
-
ant with the one specified in "Technical data" on page 38.
The gas connection, as generally the boiler installation, must be done by qualified personnel as
prescribed by the regulation in force, because a faulty gas connection could lead to fire, explosion
and other very serious damages to persons, animals and objects. The manufacturer cannot be
held responsible for any damage arising from that situation.
f
Verify what follows:
• cleaning of all system gas pipes in order to avoid the presence of work residuals that could com-
promise the correct boiler functioning;
• gas line and ramp conformity with laws and rules currently in force;
• internal and external tightness of the gas system and connections;
• supply pipe must have a section greater than or equal to the boiler one;
• supply gas must correspond to the one for which the boiler has been set: otherwise, it's manda-
tory to ask to qualified personnel to set the boiler for the correct gas type;
• an interception valve must be installed upstream the appliance.
f
Open the meter valve and purge the air that is inside the system pipes (including all the appliances).
Electrical connections of the boiler
The link of the room thermostat works with a safety extra low voltage (SELV); connect it to
the voltage free contacts of the room thermostat/chronothermostat.
On NO account must any
electrical voltage be applied
to these terminals�
All low-voltage wirings (e.g. Room Thermostat or Chronothermostat for trade) must be kept
separate from power supply cables, as to avoid boiler malfunctioning due to electrical noise. It
is advisable to use separate tubes for them.
During the connection of cables from the boiler, make sure that them are not tight and make a
slack that allows the control panel to be fully tilted.
The boiler must be connected to a 220÷240V - 50Hz electrical power supply. In any case, the power
supply voltage must be within the range –15% ... +10% from the nominal value (230V); otherwise it
may cause malfunctions or failures. It is necessary to respect the polarities L-N (Live L=brown; - Neu-
tral N=blue) - otherwise the boiler may not work - and the earth connection (yellow-green cable).
Place upstream the boiler a bipolar switch
in compliance with the regulation currently in force.
The installation must be made complying the regulation currently in force and generally with the
standard craft rules.