Operations accompanied by the symbol are always reserved to the Technician. Operations
with grey background are reserved to the Technician.
Signal
Probable causes
Suggested solutions
E01
Boiler just installed
(air mixed to gas).
Retry the ignition several times: use the
button.
When the 5 reset possibilities are over, to have 5 more, it's possible to switch off the
electrical supply to the boiler for 30 seconds, by using the purposed external switch.
The flame has extin-
guished or it did not
ignite
Restore the boiler function by using the
button.
In case of frequent blocks, verify the correct combustion, the
good state and the cleaning of the burner.
Incorrect com
-
bustion / flame de-
tachment from the
burner
Check that the Intake/Outlet Ducts and the respective terminals are
clean and in good condition, and that there are no leaks in them.
During the installation, respect the regulation prescriptions, the
slopes and the lengths (see "Flue systems" on page 22).
Note for the TECHNICIAN:
The burner flame is not detected by the control electron-
ics because it has not turned on or it has suddenly turned off, or it has detached
from the burner, because of an incorrect combustion. This can be due, in exam-
ple, to combustion product reflow into intake duct, leaks in intake/outlet ducts
or errors in sizing of ducts (ducts length out of the allowed range, and/or wrong
use of the reducer on boiler’s outlet).
E02
the boiler has over
-
heated and the
Safety Thermostat
has triggered
Restore the boiler function by using the
button. If necessary,
wait at least 20-30 minutes (to make the boiler cool) and try again.
If the lockout persists or reappears, call the Service Centre.
Verify the safety thermostat functionality. Detect the causes of
the overheating, e.g. an insufficient circulation in the primary cir-
cuit; max gas pressure out of the limits or maximum heating power
excessive for the heating system size.
E03
Incorrect flue flow
(even momentary)
Restore the boiler function by using the
button.
If the lockout persists or reappears, call the Service Centre.
check the efficiency of the flue; of the air inlet / flue outlet ducts;
of the flue flow detection device.
E05
Failure to the sys-
tem flow tempera-
ture probe.
Check the cabling of the system flow temperature probe.
Replacement of the system flow temperature probe.
E08
Max number of
boiler alarms
reached for no
flame detection.
Combustion or burner has a recursive problem. Flame detection
has been lost (with boiler block) for many times in a row.
User:
Try a boiler reset by using the
button. If the lockout
persists or reappears, call the Service Centre.