Goodrive300-01A series VFD for air compressor
Function description
-87-
Function
code
Name
Description
Default
Modify
BIT12: Pressure signal
1: Pressure signal fault; 0: Normal
BIT13: Temperature signal
1: Temperature signal fault; 0: Normal
BIT14: Low-temperature protection
1: Low-temperature alarm; 0: Normal
BIT15: Master state
1: Run; 0: Stop
P19.14
Signal state 2
0
–0xFFFF
BIT0: Maintenance reminder of part 1
1: Maintenance required; 0: Normal
BIT1: Maintenance reminder of part 2
1: Maintenance required; 0: Normal
BIT2: Maintenance reminder of part 3
1: Maintenance required; 0: Normal
BIT3: Maintenance reminder of part 4
1: Maintenance required; 0: Normal
BIT4: Maintenance reminder of part 5
1: Maintenance required; 0: Normal
BIT5: Auxiliary pressure signal
1: Auxiliary pressure signal fault; 0: Normal
BIT6: Auxiliary temperature signal
1: Auxiliary temperature signal fault; 0: Normal
BIT7: Auxiliary pressure pre-alarm signal
1: Pressure pre-alarm; 0: Normal
BIT8: Auxiliary temperature pre-alarm signal
1: Temperature pre-alarm; 0: Normal
BIT9: Auxiliary pressure alarm signal
1: Pressure alarm; 0: Normal
BIT10: Auxiliary temperature alarm signal
1: Temperature alarm; 0: Normal
BIT11: Maintenance timeout remainder
1: Maintenance timeout remainder; 0: Normal
BIT12: Phase sequence remainder
1: Fault; 0: Normal
BIT13: Reserved
BIT14: PTC overtemperature signal
1: PTC overtemperature alarm; 0: Normal
0
●