Goodrive300-01A series VFD for air compressor
Function description
-43-
Function
code
Name
Description
Default
Modify
P03.08
Power
generation slip
compensation
coefficient of
vector control
50%
–200.0%
100%
○
P03.09
ACR
proportional
coefficient P
0
–65535
The default value of
different within differing power ranges, and
the default value will be configured as below
after autotuning and setting power range via
the touch screen.
(reference)
value
(reference)
Motor
power
2000
1000
7.5
–22kW
2500
1500
30
–37kW
3000
1500
45
–90kW
3500
2000
110
–132kW
4000
2000
160
–315
kW
Model
depended
○
P03.10
ACR integral
coefficient I
Model
depended
○
P03.11
Torque setting
method
0: Torque control is invalid
1: Keypad (P03.12)
2: P1- (100% corresponding to three times
the motor rated current)
3: Reserved
4: P2- (100% corresponding to three times
the motor rated current)
5
–6: Reserved
7: Modbus communication (same as the
above)
8
–10: Reserved
0
○
P03.12
Torque set
through keypad
-300.0%
–300.0% (of the motor rated current)
50.0%
○
P03.13
Torque
reference filter
time
0.000
–10.000s
0.010s
○
P03.14
Setting source
of forward
0: Keypad (P03.16)
1: P1- (100% corresponding to the max.
0
○
Содержание GD300-01A