Goodrive300-01A series VFD for air compressor
External optional accessories
-137-
User parameter
Initial value
Function
temperature
fan is started.
Loading delay
10S
After the startup, the air compressor runs with load with this
specified delay.
Load/unload mode
Automatic
If the manual mode is used, both load and unload need to be
manually performed after the air compressor is started.
If the automatic mode is used, the air compressor
automatically loads or unloads depending on the pressure
after being started.
Sleep function
Enabling
Disable/Enable
No-load delay
300S
Max. continuous empty-load running time allowed by the air
compressor. If the time is reached, the air compressor
enters the sleep state.
Stop delay
0S
Before stop, the device runs at the empty-load frequency
and stops with this specified delay.
Restart delay
30s
After the device stops, the device determines whether to
start with this specified delay.
Set pressure
0.70 MPa
Air supply pressure during stable running. The VFD controls
the running frequency according to this pressure so as to
implement constant pressure for air supply.
Unloading pressure
0.80 MPa
If the pressure is higher than this value when the air
compressor is running, the VFD controls the air compressor
to run without load.
Loading pressure
0.60 MPa
If the VFD detects the pressure is lower than this value when
the air compressor is running without load, the VFD controls
the air compressor to run with load. If the VFD detects the
pressure is lower than this value when the air compressor is
sleeping, the master is waken up.
Power consumption
/
All the electricity consumption (kWh) of the VFD system.
The value is automatically generated and cannot be set, but
it can be cleared.
Accumulated running
time
/
Accumulative running time (hours) of the VFD system. The
value is automatically generated and cannot be set, but it
can be cleared.
Timing switch setting
Press Set to access the corresponding interface.
Startup time: Scheduled time when the device is
automatically started.
Shutdown time: Scheduled time when the device is
automatically stopped.