Goodrive300-01A series VFD for air compressor
Function description
-70-
Function
code
Name
Description
Default
Modify
P11.04
Overvoltage stall
protection voltage
120
–150% (standard bus voltage) (380V)
140%
○
P11.05
Current limit
selection
0x00
–0x11
Ones: Current-limit action selection
0: Current-limit action is invalid
1: Current-limit action is always valid
Tens: Hardware current-limit overload alarm
selection
0: Hardware current-limit overload alarm is
valid
1: Hardware current-limit overload alarm is
invalid
01
◎
P11.06
Automatic
current-limit level
50.0
–200.0%
160.0%
◎
P11.07
Frequency drop
rate at current limit
0.00
–50.00Hz/s
10.00Hz/s
◎
P11.08
Pre-alarm
selection for
VFD/motor
overload/underload
0x000
–0x131
LED ones:
0: Motor overload/underload pre-alarm,
relative to the motor rated current,
1: VFD overload/underload pre-alarm,
relative to the VFD rated current
LED tens:
0: The VFD keeps running after reporting an
overload/underload alarm.
1: The VFD keeps running after reporting an
underload alarm, but it stops running after
reporting an overload alarm.
2: The VFD keeps running after reporting an
overload alarm, but it stops running after
reporting an underload alarm.
3: The VFD stops running after reporting an
overload/underload alarm.
LED hundreds:
0: Always detect
1: Detect only in constant speed running
0x000
○
P11.09
Overload
pre-alarm
detection level
–200%
G type:
150%
○
Содержание GD300-01A