Goodrive300-01A series VFD for air compressor
Safety precautions
-2-
Do not perform wiring, inspection or component replacement when power
supply is applied. Ensure that all the input power supplies are disconnected
before wiring and inspection, and always wait for at least the time designated
on the VFD or until the DC bus voltage is less than 36V. The waiting time is
shown as below.
VFD model
Minimum waiting time
380V
7.5kW-110kW
5 minutes
380V
132kW-315kW
15 minutes
380V
Higher than 350kW
25 minutes
660V
22kW-132kW
5 minutes
660V
160kW-350kW
15 minutes
660V
400kW-630kW
25 minutes
Do not refit the VFD unless authorized; otherwise fire, electric shock or other
injury may result.
The base of the radiator may become hot during running. Do not touch to
avoid hurt.
The electrical parts and components inside the VFD are electrostatic
sensitive. Take measurements to prevent electrostatic discharge when
performing related operations.
1.4.1 Delivery and installation
Do not install the VFD on inflammables. In addition, prevent the VFD from
contacting or adhering to inflammables.
Connect the optional brake parts (brake resistors, brake units or feedback
units) according to the wiring diagram.
Do not operate on the VFD if there is any damage or components loss to the
VFD.
Do not touch the VFD with wet items or body; otherwise, electric shock may
occur.
Note:
Select appropriate moving and installing tools to ensure a safe and normal running of the VFD
and avoid physical injury or death. To ensure personal safety, the installer must take
mechanical protective measures, such as wearing exposure shoes and working uniforms.
Ensure the VFD suffers no physical impact or vibration during moving and installation.
Do not carry the VFD by its front cover only as the cover may fall off.
Installation site must be away from children and other public places.
The application environment should be proper and appropriate.
Содержание GD300-01A
Страница 1: ......
Страница 187: ...6 6 0 0 1 0 0 7 6 1...