Goodrive300-01A series VFD for air compressor
External optional accessories
-153-
03.17 16:02:35
Home
Please enter current password:
Return
Confirm
000
0
03.17 16:02:35
Home
Confirm to clear the realtime alarm info?
Return
Confirm
Figure B-47 Alarm record clearing interface
Note
: The real-time alarm interface can keep a maximum of 50 fault records due to the restriction of
memory. When the number of fault records exceed 50, if you do not manually clear these extra
records, the earliest fault records will be automatically overwritten.
B.2.5.4 Historic alarm interface
The fault information in the historic alarm interface is the same as that in the real-time alarm interface.
The only difference is that the historic alarm interface always keeps the fault records even if the
keypad is powered off, while the real-time alarm interface clears all the fault records if the keypad is
powered off.
Note
: The historic alarm interface can keep a maximum of 500 fault records due to the restriction of
memory. When the number of fault records exceed 500, if you do not manually clear these extra
records, the earliest fault records will be automatically overwritten.
B.2.6 VFD information
Enter the VFD information interface through the main menu, as shown in the following figure.