Goodrive300-01A series VFD for air compressor
External optional accessories
-144-
Protection
parameter
Initial
value
Function
Prealarm pressure 0.90Mpa
When the actual air supply pressure is higher than this pressure,
a pre-alarm is reported.
Alarm pressure
1.00Mpa
When the actual air supply pressure is higher than this pressure,
an alarm is reported, and the device is stopped.
Auxiliary
temperature
prealarm
105°C
When the detected temperature is higher than this temperature,
a pre-alarm is reported. This parameter is valid only after it is
enabled in system configuration.
Auxiliary
temperature alarm
110°C
When the detected temperature is higher than this temperature,
an alarm is reported, and the device is stopped. This parameter
is valid only after it is enabled in system configuration.
Auxiliary pressure
prealarm
0.90Mpa
When the detected pressure is higher than this pressure, a
pre-alarm is reported. This parameter is valid only after it is
enabled in system configuration.
Auxiliary pressure
alarm
1.00Mpa
When the detected pressure is higher than this pressure, an
alarm is reported. This parameter is valid only after it is enabled
in system configuration.
Low temperature
protection
threshold
-10°C
When the detected temperature is lower than this temperature, a
low temperature pre-alarm is reported. This parameter is valid
only after it is enabled in system configuration.
Current auxiliary
temperature
/
It displays the auxiliary temperature that is currently detected.
Current auxiliary
pressure
/
It displays the auxiliary pressure that is currently detected.
Enable auxiliary
temperature
protection
Disable
Disable/Enable
Enable auxiliary
pressure protection
Disable
Disable/Enable
2. You can edit parameters only after entering the correct administrator password.