Installation and Programming Manual
Options and programming methods
53
Table 33:
Event type
Name
Occurs when...
Restores when ...
Number of events
Pulse
events
Zone alarm
A zone generates an alarm
A zone restores
One event for each
zone
no
Terminal tamper
A terminal detects tamper (short-circuit or
wire cutting)
A terminal restores
One event for each
terminal
no
Partition alarm
A 24h zone which belongs to the partition
generates an alarm, or a zone which belongs
to the partition generates an alarm during
Away mode.
All the zones belonging to the partition
restore (reset).
One event for each
partition
no
StayPartit.alarm
A zone which belongs to a partition armed in
Stay or Instant mode, generates an alarm.
All the zones belonging to the partition
restore (reset).
One event for each
partition
no
Partition tamper
A zone which belongs to the partition detects
tamper (short-circuit or wire cutting).
All the zones belonging to the partition
restore (reset).
One event for each
partition
no
Zone bypass
A zone is inhibited
A zone is enabled (switched On)
One event for each
zone
no
Real-time zone
The electrical status of a zone switches from
standby to alarm
The electrical status of a zone switches
from alarm to standby
One event for each
zone
no
The event is independent of the zone type and the armed/disarmed status of the
partitions.
Partit.not ready
A zone which belongs to the partition is not in
standby status.
All the zones belonging to the partition
are in standby status.
One event for each
partition
no
Away arm request
A request is made to arm the interior and
perimeter zones of the partition
A request is made to disarm the
partition
One event for each
partition
Yes
Overtime request
A request is made to arm the partition in Stay
mode (perimeter zones only) or in Instant
mode
A request is made to disarm the
partition
One event for each
partition
Yes
Partit.AwayArmed
The partition interior and perimeter zones
have been armed effectively
The partition has been disarmed
effectively
One event for each
partition
no
Partit.StayArmed
armed
The partition has been armed effectively in
Stay or Instant mode
The partition has been disarmed
effectively
One event for each
partition
no
Partition reset
A request is made to reset the partition
One event for each
partition
Yes
Exit time
The partition exit time is running
The partition exit time expires
One event for each
partition
no
Entry time
The partition entry time is running
The partition entry time expires
One event for each
partition
no
Pre-arm time
The partition Pre-arm time is running
The partition Pre-arm time expires
One event for each
partition
no
Overtime request
A request for overtime relating to the
partition is made
One event for each
partition
Yes
Chime
A chime zone belonging to the partition is
violated
One event for each
partition
Yes
Forced arming
At the time of an arming command, relating
to one or more partitions, there are open
zones on the partition/partitions involved, or
there are other conditions present which
lower system security, nonetheless, the user
arms the system.
One event for each
partition
Yes
Failed to arm
The “OpenZonesArmLock” option is enabled
at the time of a partition arming command
and there is at least one open zone on the
partition/s involved.
or
when one or more of the conditions described
in “LossTamp.ongoing” is present (refer to
“FaultNotReady”, paragraph
6-25 Other
parameters
).
One event for each
partition
Yes
Valid code
A user-code PIN entered at a keypad is
recognized as valid
One event for each
code
Yes
Valid key
A key used at a reader is recognized as valid
on the reader
One event for each
key
Yes
Valid Code AtKeyp.
A user-code PIN entered at a keypad is
recognized as valid on the keypad
One event for each
keypad
Yes
ValidKeyAtReader
A key used at a reader is recognized as valid
on the reader
One event for each
reader
Yes
Partition code
A user-code PIN entered at a keypad is
recognized as valid on the partition
One event for each
partition
Yes
Partition key
A key used at a reader is recognized as valid
on the partition
One event for each
partition
Yes
Failed call
A call is not answered
One event for each
contact telephone
number
Yes
Timer activated
The timer is enabled (On)
The timer is disabled (Off)
One event for each
timer
no
Thermostat ON
The activation conditions set for the keypad
thermostat occur.
The deactivation conditions set for the
keypad thermostat occur.
One event for each
keypad
no
Содержание GameOver SmartLiving 1050