Installation and Programming Manual
Compliancy with the regulations in force
95
Appendix G
COMPLIANCY WITH THE
REGULATIONS IN FORCE
In order to guarantee compliancy with the regulations in force, you must adhere
to the following guidelines:
•
nBy/X readers must be equipped with devices which protect them against the
forced-opening and dislodgement of their casings from their locations, in
compliance with Level 2, as indicated in paragraph
3-2-5 Installing nBy/X
readers
.
•
The Tamper NO dislodgement-tamper-protection device of the control panel
must be installed.
•
JOY, nCode and Concept keypads must be equipped with enabled tamper-
protection devices, as indicated in paragraph
3-3-1 Addressing the keypads
.
•
FLEX5/U expansion boards must be either mounted inside the metal enclosure
of the 1050L or 10100L control panel, or equipped with devices which protect
them against the forced-opening of their casings and dislodgement from their
locations, in compliance with Performance level 2.
•
The lines relating to the intrusion-detection zones must be configured as
'Double balancing' with double EOL resistors, or as Single balancing with
single EOL resistor. They must also be equipped with devices which protect
them against the forced-opening of their casings.
•
Terminal tamper, peripheral tamper and control-panel tamper events must
trigger audible signals (sounder signals) for a period of not less than 3
minutes.
•
The output activated by the previously mentioned tamper events must be
different from the output activated by alarms signals.
•
All Code PINs must have 6 digits.
•
If a Timer is used for automatic-arming operations, the Pre-arm times must be
programmed separately for each partition (the Pre-arm time must not be set
at 0).
CEI 79-2
In particular, in order to guarantee CEI 79-2 compliancy of devices, the following
options must be programmed as follows.
•
The following options must not be activated in the “Panel Options” section:
•• ReaderBuzzer OFF
•• BypassAlsoTamper
•• OpenZonesArmLock
•• 50131ReaderLedOFF
•• 50131StatHidden
•• 50131IconsHidden
•• 50131AlarDelayed
•• 50131WarnLedMem
•
All of the “FaultsNotReady” options - from the “Other parameters” section -
must be disabled.
•
The “Requires code” option - from the “Keypads - Choose peripheral - Options”
section - must be enabled for every keypad and shortcut in use.
•
The “Entry Time” parameter of each partition must be no more than 60
seconds.
EN50131
Compliancy with EN50131 Grade 2 is guaranteed by observing the following
guidelines.
•
In the “Panel options” section, enable:
•• Keypad lockout
•• OpenZonesArmLock
•• NoUserTamp.reset
•• 50131ReaderLedOFF