30
Installation
Installation and Programming Manual
7. If you wish to assign an address to another reader, hold a valid key in the
vicinity of the reader and work through points 4 to 6.
8. End the reader-address programming phase (exit “Prog. address” via key-
pad, or click on “Stop reader address setup”, if you are using the Smart-
League software).
3-4
Auto-enrolling peripherals
The peripherals connected to the BUS are enrolled automatically in the following
situations:
•
on first startup (refer to
Chapter 4 - First power up
)
•
if the SERV jumper is inserted (refer to paragraph
3-1-10 Maintenance status
)
•
via the Installer menu (refer to paragraph
6-23 Default settings
) >
Type in Code
(Installer)
, PROGRAMMING Default settings
, Auto Periph
.
3-5
Wiring and balancing
alarm detectors
The wiring and respective balancing method depend on the type of detector you
are installing, and the level of protection you wish to achieve. The detectors can
be powered through:
•
terminals [+AUX/12V] and [-/GND] on the control panel
•
terminals [+AUX/12V] and [-/GND] on FLEX5 expansions
•
terminal [+/12V] and terminals [-/GND] on keypads
•
from any 12V ancillary source on condition that its GND reference is in
common with that of the control panel.
The resistors used for balancing are:
•• 3K9
W
1/4W
•• 6K8
W
1/4W
The following Table indicates the protection level of each detector type and the
balancing options provided by the control panel:
3-5-1
N.C./N.O. Balancing
For N.C. (normally closed) and N.O. balancing (normally open), it is
possible to detect two distinct zone conditions:
•
standby
•
alarm
For each of these, the control panel reads different resistance values on
the terminal, expressed below in Ohm.
If you wish the detector to signal tamper events, connect the detector
“Tamper” terminal to a “24h” zone on the control panel.
Table 26:
Protection level
BALANCING
N.O.
N.C.
Single
Double
Double
zone
Double
zone
with EOL
Infrared or
Double
technology
very low
low
medium
(*)
high
medium
high
Magnetic contact
very low
low
medium
medium
high
3K9
Ω
1/4W
6K8
Ω
1/4W
Red
White
Orange
Gold
Red
Grey
Blue
Gold
(*) Single balancing provides
the same level of protection as
Double balancing, when the
tamper contact of the
detector is connected
to a balanced zone on
the control panel.
W
W
N.C.
N.O.
> 2 x 3900 + 6800
alarm
standby
> 2 x 3900 + 6800
alarm
standby
3900 + 6800
alarm
alarm
2 x 3900
alarm
alarm
3900
standby
alarm
0
standby
alarm
Alarm
+12V GND
Tamper