24
Installation
Installation and Programming Manual
3-1-10
Maintenance status
There are two distinct positions for the Service jumper (
Table 4: Control panels -
description of parts, Q
):
1. “RUN” (control panel operating normally)
2. “SERV” (control panel ready for maintenance work)
The keypads indicate maintenance status (jumper in “SERV” position) by showing
the “Maintenance” message on the first line on the display next to the keypad
address. The address of the built-in reader (if enabled) of JOY/MAX keypads will
also be shown.
Under these circumstances, the control panel:
•
Forces the relay output on the motherboard (
Table 5: Control panel - terminal
board, 10-11-12
) to standby status.
•
Does not activate the outputs (and will force to standby any active outputs)
triggered by:
•• alarm or zone/partition tamper
•• peripheral tamper
•• open/dislodged panel tamper
•
It allows initialization of the keypad address programming phase.
•
It allows initialization of the reader address programming phase.
•
It initializes automatically the auto-enrolment of the peripherals connected to
the BUS at 10 seconds intervals. It allows assignment of the addresses to the
peripherals connected to the BUS and, at 10 second intervals, enrolls the
peripherals it finds.
•
The control panel will not reset the BUS in an attempt to retrieve peripherals
in the event of peripheral loss.
•
It will continue to operate as normal, except under the aforesaid
circumstances.
3-2
Connecting peripherals
3-2-1
The I-BUS line wiring
The SmartLiving peripherals (keypads, readers, expansions, sounderflashers,
transceivers, isolators and GSM communicator) must be connected to the control
panel via the I-BUS.
The wiring diagram opposite provides an example of a 4-wire connection (using
shielded cable) between a control panel and its peripherals.
The cable specifications depend on the length of the BUS (from the panel
terminals to the most distant point), Baud rate and the load current draw.
The maximum wire length of the I-BUS depends on the deployment of the
peripherals connected to the line and their specific current draw (in particular the
keypads and expansion boards). The power to peripherals and detectors can be
supplied by external power stations or by the line itself.
Furthermore, the speed of the communication BUS (Baud rate) can be modified
by means of the SmartLeague programming software. If the BUS is not used to
power the peripherals and their loads, the maximum wire length is 300 meters @
250kbs, regardless of the number of peripherals involved.
An intermediate speed (125kbs) can support a single section of 700 meters.
Position 1 Position 2
Mainten K03 P05
DASIDASI--
Keypad address
Reader address
Table 25:
Recommended cable
Cable
AF CEI 20-22 II
n. wires
Section
(mm
2
)
I-BUS
terminal
4 wire cable +
shield
2
0.5
+ -
2
0.22
D S
6 wire cable +
shield
2
0.5
+ -
2
0.22
D S
2
0.22
available
6 wire cable +
shield
2
0.75
+ -
2
0.22
D S
2
0.22
available
D S -