7 BACnet Communication
3-138
WindO/I-NV4 User’s Manual
Analog Value Object
Present_Value of the Analog Value object can be used as Present_Value of both the Analog Input and Analog Output
objects. Present_Value is a Float32(F) numeric value.
The following diagram illustrates the concept when device addresses are allocated to Present_Value of the Analog
Value object and the temperature of an office air conditioner is temporarily lowered from the base temperature
(27.0°C) to 26.5°C.
Example: When #D0000 is allocated to the Present_Value device, #D0010 is allocated to the top device for priority
and trigger, and Float32(F) is allocated to the conversion type, the device addresses are allocated as
follows: #D0000 is the Present_Value for reading, #D0002 is the Present_Value for writing, #D0010 is the
Device for priority, and #D0011 is the Device for write trigger.
Writing the Value of a Device Address to Present_Value
(1) When the value of the Device for write trigger (#D0011) is 1, writes the value of the Present_Value for writing
(#D0002) to the Priority_Array at the index number stored in the Device for priority (#D0010).
(2) The Device for write trigger (#D0011) is automatically reset to 0.
(3) Priority_Array with the smallest index number out of all non-NULL(00h) values is element 1 (26.5), so 26.5 is used
as the value of Present_Value.
BACnet objects
Device addresses
BACnet device
Analog Value
object
Present_Value:
26.5
#D0000: XXXX
#D0002:
26.5
D0010:
1
D0011: 1
Reflected
Read value:
26.5
MICRO/I
∙∙∙
Priority_Array
26.5
1
NULL(00h)
2
27.0
3
16
(1)
(2)
(3)
Present_Value
for reading
Present_Value
for writing
Device for priority
Device for write trigger
Содержание WindO/I-NV4
Страница 1: ...B 1701 16 User s Manual...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic ANSI 1257 Cyrillic ANSI 1251...
Страница 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Страница 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Страница 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Страница 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Страница 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Страница 522: ...5 Key Button 8 102 WindO I NV4 User s Manual Password Input These keys switch the user on the Password Input Screen...
Страница 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Страница 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Страница 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Страница 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Страница 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Страница 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Страница 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Страница 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Страница 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Страница 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Страница 1694: ...5 HG1P 35 80 WindO I NV4 User s Manual 5 6 Dimensions Unit mm Cable Dimensions 191 169 56 70 6 51 55 7...
Страница 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...