1 HG2J-7U
35-10
WindO/I-NV4 User’s Manual
1.8 Wiring
●
Power Supply Terminal
• Pin assignment is shown in the following table.
• Use applicable cables for wiring and recommended ferrules (made by IDEC, Weidmüller or Phoenix Contact) as
follows.
●
Caution when inserting and removing wires
• When connecting a wire that has not been treated with a tip, such as a stranded wire, you can connect it by
inserting the wire all the way in while pressing the pusher, and then releasing the pusher.
• When connecting wires with ferrules, connect the ferrules to the terminal block so that the long side is horizontal.
(See the figure below.)
• When pulling out the wire, use a flat blade screwdriver, etc., and pull the wire straight out while pressing the
pusher with about 20 N of force.
• Be careful not to damage the push-in terminals.
• When pressing the pusher, do not apply more than 40N of force. Also, do not pull out the wire without pressing the
pusher.
*1 Strip the sheath of the wire 7 to 9 mm from the end.
CAUTION
• Turn off the power supply before wiring.
• Make the wiring as short as possible and run all wires as far away as possible from high-voltage
and large-current cables. Follow all the procedures and precautions when wiring the HG2J-7U.
• Separate the HG2J-7U power supply wiring from the power lines of I/O devices and motor
equipment.
• Ground the functional earth terminal to make sure of correct operation.
• Use the SELV (Safety Extra-Low Voltage) circuit and LIM (Limited Energy) circuit for power supply.
• Use wire copper conductor only.
+
Power supply 12V / 24V DC
-
Power supply 0V (0V)
Functional Earth (FE)
Applicable cable
AWG14 to AWG28
Conductor Type
Solid wire or Stranded wire
Wire Strip Length
7 to 9 mm
Recommended ferrule
ST3L-H025-12WJ
S3TL-H034-12WT
S3TL-H05-14WA
S3TL-H075-14WW
(IDEC)
H0,25/12 HBL
H0,34/12 TK
H0,5/14 OR
H0,75/14 W
(Weidmüller)
AI 0,25-8YE
AI 0,34-8TQ
AI 0,5-8WH
AI 0,75-8GY
(Phoenix Contact)
Power Supply Terminal
Serial Interface (COM)
OK
NG
OK
NG
Pusher
(Push button for removal)
7 to 9 mm
Содержание WindO/I-NV4
Страница 1: ...B 1701 16 User s Manual...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic ANSI 1257 Cyrillic ANSI 1251...
Страница 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Страница 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Страница 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Страница 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Страница 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Страница 522: ...5 Key Button 8 102 WindO I NV4 User s Manual Password Input These keys switch the user on the Password Input Screen...
Страница 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Страница 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Страница 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Страница 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Страница 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Страница 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Страница 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Страница 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Страница 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Страница 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Страница 1694: ...5 HG1P 35 80 WindO I NV4 User s Manual 5 6 Dimensions Unit mm Cable Dimensions 191 169 56 70 6 51 55 7...
Страница 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...