5 User Communication
3-44
WindO/I-NV4 User’s Manual
+0
14
Receiving Time
Out
1 frame of data is not received even when the preset
Receiving Time Out duration has passed after the
Trigger Condition is satisfied.
Check the transmission data
from the external device.
15
Receiving
Character Time
Out
While 1 frame of data is being received, even after the
time out period—the specified time interval between
receiving data (from when 1 frame of data has been
received to when the next frame of data starts to be
received)—has elapsed, the next frame of data does
not start to be received.
Check the transmission data
from the external device.
Address
number
Function
Description
+1
Receive Data Size (bytes)
Stores the size of receive data.
Address
number
Bit
Function
Cause
Solution
After the Receiving Character Time Out duration has elapsed, the receive data is analyzed. When the Error
Information bit changes to 1, data is not received, and the Receiving Completed Device Address does not change to 1.
Transmission Wait (x100 msec):
Specify the wait time (0 to 255) from when the trigger condition is satisfied to when the data is transmitted. This
can be configured only when
TXD
is selected as
Type
on the Command Settings dialog box.
After the Transmission Wait duration has elapsed from when the trigger condition is satisfied, transmission starts.
Example: When
Trigger Type
in
Trigger Condition
is
Rising-edge
and
Device Address
is LM100
Receiving Time Out (x100 msec):
Set the time out (0 to 255) from when the trigger condition is satisfied to when 1 frame of data has been received.
A frame refers to a data string from the beginning to the end of a command. If the Receiving Character Time Out
is set to 0, it is not monitored.
This can be configured only when
RXD
is selected as
Type
, and
While ON
,
While OFF
, or
While satisfying
the condition
is selected in
Trigger Type
.
When 1 frame of data could not be received, even though the Receiving Time Out duration has elapsed from
when the trigger condition is satisfied, the value of the Receiving Time Out of the Status Device Address (address
0, bit 14) changes to 1. When the Receiving Time Out duration elapses, the value of the Completed
Device Address does not change to 1, and the receive data is not processed.
When the trigger condition again changes from not satisfied to satisfied, the value of the Receiving Time Out of
the Status Device Address (address 0, bit 14) changes to 0. When the value of this bit is not 0, the
Receiving Time Out cannot be detected.
Transmission command
Value of Device Address LM100
when Trigger Condition is
Rising-edge
1
0
Transmission data 1 frame
Transmission
Wait duration
Transmission data 1 frame
Transmission
Wait duration
Value of Device Address when
Trigger Condition is
While ON
1
0
1
0
Receiving Time Out duration
Value of the Receiving Time Out
(address 0, bit14)
of the Status Device Address
Содержание WindO/I-NV4
Страница 1: ...B 1701 16 User s Manual...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic ANSI 1257 Cyrillic ANSI 1251...
Страница 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Страница 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Страница 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Страница 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Страница 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Страница 522: ...5 Key Button 8 102 WindO I NV4 User s Manual Password Input These keys switch the user on the Password Input Screen...
Страница 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Страница 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Страница 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Страница 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Страница 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Страница 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Страница 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Страница 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Страница 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Страница 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Страница 1694: ...5 HG1P 35 80 WindO I NV4 User s Manual 5 6 Dimensions Unit mm Cable Dimensions 191 169 56 70 6 51 55 7...
Страница 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...