4 Using the Data
14-46
WindO/I-NV4 User’s Manual
• The data size for each row is counted as 2 bytes for full-width characters, 1 byte for half-width characters,
and 2 bytes for newlines. The total for each row is the total amount of space for the file.
• A space is inserted before the year in the data row.
• The display type for the date and time differs according to the language configured in
Project Settings
,
on the
Project Details
tab, in
Language
.
Japanese: YYYY/MM/DD hh:mm:ss
Western,
Simplified Chinese, Traditional Chinese, Hangul, Central European, Baltic, Cyrillic
:
MM/DD/YYYY hh:mm:ss
• The output values of the data row will depend on
Data Type
of the data.
- When
Data Type
of the data is
String(S)
The values of the set amount of words of device addresses stored from
Top Device Address
are
converted to a string and output.
However, if NULL(00h) appears in the string, the characters after NULL(00h) are not output.
The order of characters output to the CSV file is set according to
Storage Method of String Data
on
the
System
tab in the
Project Settings
dialog box.
Example: Starting device address: LDR0, number of words: 3
Stored values: LDR0=0x3132, LDR1=0x3334, LDR2=0x3536 => Output value: 123456
Stored values: LDR0=0x3132, LDR1=0x3300, LDR2=0x3435 => Output value: 123
If the string contains the following codes, the entire string will be enclosed with double quotation
marks (") and output.
Comma (,)
Newline codes (CR, LF, and CR+LF)
Double quotation mark (")
If the string contains a double quotation mark ("), a double quotation mark (") will be added in front of
it.
Example: Starting device address: LDR0, number of words: 3
Stored values: LDR0=0x312C, LDR1=0x3334, LDR2=0x0000 => Output value: "1,34"
Stored values: LDR0=0x310D, LDR1=0x3334, LDR2=0x0000 => Output value: "1[CR]34"
Stored values: LDR0=0x3122, LDR1=0x3334, LDR2=0x0000 => Output value: "1""34"
- When
Data Type
is
UBIN16(W)
,
BIN16(I)
,
UBIN32(D)
,
BIN32(L)
,
BCD4(B)
,
BCD8(EB)
, or
Float32(F)
The value is output according to the setting of
Display Type
.
The zeros in the value are suppressed.
If the stored value exceeds the number of display digits, the upper portion of the value is cut and only
the lower portion of the value is output for data types other than
Float32(F)
(source data: integer
value). For
Float32(F)
(source data: decimal value), the upper value of the integer part and lower
value of the decimal part are cut and the value is output in the number of display digits.
If an invalid number has been stored, #N/A is output.
If a comma (,) is used as the decimal point, the entire string is enclosed with double quotation marks
(") and output.
Example: Starting device address: LDR0, number of words: 1
Stored value: LDR0=0x04D2
Data Type
is
UBIN16(W)
,
Display Digits
is 5 => Output value: 1234
Data Type
is
UBIN16(W)
,
Display Digits
is 2 => Output value: 34
Data Type
is
UBIN16(W)
,
Display Digits
is 2,
Floating Digits
is 1,
Floating Symbol
is . (dot) => Output value: 3.4
Data Type
is
UBIN16(W)
,
Display Digits
is 2,
Floating Digits
is 1,
Floating Symbol
is , (comma) => Output value: "3,4"
Data Type
is
BCD4(B)
,
Display Digits
is 4 => Output value: #N/A
Example: Starting device address: LDR0, number of words: 2
Stored values: LDR0=0xA000, LDR1=0x0000
Data Type
is
BIN16(I)
,
Display Digits
is 5 => Output value: -24576
Data Type
is
BIN16(I)
,
Display Digits
is 2 => Output value: -76
Data Type
is
BIN16(I)
,
Display Digits
is 2,
Floating Digits
is 1,
Floating Symbol
is .
(dot) => Output value: -7.6
Data Type
is
Float32(F)
,
Display Digits
is 10 => Output value: #N/A
Содержание WindO/I-NV4
Страница 1: ...B 1701 16 User s Manual...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic ANSI 1257 Cyrillic ANSI 1251...
Страница 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Страница 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Страница 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Страница 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Страница 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Страница 522: ...5 Key Button 8 102 WindO I NV4 User s Manual Password Input These keys switch the user on the Password Input Screen...
Страница 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Страница 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Страница 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Страница 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Страница 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Страница 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Страница 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Страница 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Страница 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Страница 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Страница 1694: ...5 HG1P 35 80 WindO I NV4 User s Manual 5 6 Dimensions Unit mm Cable Dimensions 191 169 56 70 6 51 55 7...
Страница 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...