AC Detection and AC Monitoring
Main Line Survey
Major disturbances are defined as follows:
A 35 % or more dip in the minimum nominal voltage.
When this input is under the specified threshold during 40 ms, an AC failure is detected by the PCC card
and the AC fail signal is generated. Two types of AC failure can be reported to the MOSS:
1. Valid AC failure:
a. Transient AC failure:
A failure defined as above (40 ms minimum) with a duration lower than T2 (45 ms).
b. AC failure:
An AC failure longer than T2 (45 ms). The whole machine is powered OFF.
2. Invalid AC failure:
The PCC card detects an AC failure, but the AC is still present after two seconds (false AC failure
detection).
────────────┐
.
│
.
│
AC FAIL
.
└──────────────
.
.
.
.
───────────────────┐
.
.
│
.
.
│
PS DC OUTPUT
.
.
└───────
.
.
.
.
.
.
.
.
.
Tð
T1
T2
T0
: At this time the AC is going under the threshold
T1
: At this time the AC failure detection occurs
T2
: At this time the DC output is falling down
T0-T1 : AC failure detection time (40 ms minimum)
T0-T2 : PS hold up time (45 ms minimum)
10-26
IBM 3745 Models 130, 150, 160, 170, and 17A: Hardware Maintenance Reference
Содержание 3745 Series
Страница 2: ......
Страница 12: ...x IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 14: ...xii IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 18: ...xvi IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 21: ...3745 Models 130 150 160 and 170 Data Flow Chapter 1 General Information 1 3 ...
Страница 149: ...For RACs 241 to 244 ERR bits Data received from the adapter Chapter 3 Buses 3 57 ...
Страница 166: ...4 14 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 169: ...Chapter 4 Transmission Subsystem TSS 4 17 ...
Страница 255: ...The HPTSS in 3745 Models 130 150 160 and 170 Data Flow Chapter 5 High Performance Transmission Subsystem HPTSS 5 3 ...
Страница 303: ...Figure 6 8 Ring to Ring via Bridge Example 2 Typical Multi Floor Wiring Chapter 6 The Token Ring Subsystem 6 9 ...
Страница 322: ...6 28 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 348: ...7 26 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 625: ...The ESS in 3745 Models 130 150 160 and 170 Data Flow Chapter 12 Ethernet Subsystem ESS 12 3 ...
Страница 668: ...Problem Determination Aid 12 46 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 674: ...X 6 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 708: ......
Страница 711: ......
Страница 712: ...IBM Part Number 03F5010 Printed in Denmark by IBM Danmark A S ð3F5ð1ð SY33 2ð66 4 ...