Power Mode of Operation
Local Mode
In local mode (3 at the power control window) the only way to power ON/OFF the 3745 is to do it manu-
ally from the control panel.
In this mode, for safety reasons, the Automatic Restart and the scheduled power ON functions are not
available. In this mode the Power ON Reset of the machine is available from the control panel.
Host Mode
In host mode (1 at the power control window) the only way to power ON/OFF the 3745 is to do it from the
locally-attached hosts, via external control cables.
When any of these hosts goes ON, the 3745 powers ON with a power pick command.
When all attached hosts have turned OFF (all power hold dropped) the 3745 turns OFF.
An EPO plug Part 8482303 must be installed in position J5 if no host EPO cables are installed. This plug
prevents powering OFF the 3745 if the power control is set to position 1 (host mode), when no EPO
cables are installed.
In this mode, the automatic restart and power ON retry functions are available.
Network Mode
In network mode (2 at the power control window) and only in this mode, the scheduled power ON function
is available. As for all the other communication controllers, in this mode you can power ON the 3745
manually from the control panel, and you can power OFF the 3745 through the NCP (RPO function also
called RMPO for VTAM). The scheduled power ON function does not disable the manual power ON or
RPO functions. This means that you always have the ability to power ON the 3745 manually before the
scheduled power ON time.
In this mode, the automatic restart and power ON retry functions are available.
In this mode the Power ON Reset of the machine is available from the control panel.
10-20
IBM 3745 Models 130, 150, 160, 170, and 17A: Hardware Maintenance Reference
Содержание 3745 Series
Страница 2: ......
Страница 12: ...x IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 14: ...xii IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 18: ...xvi IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 21: ...3745 Models 130 150 160 and 170 Data Flow Chapter 1 General Information 1 3 ...
Страница 149: ...For RACs 241 to 244 ERR bits Data received from the adapter Chapter 3 Buses 3 57 ...
Страница 166: ...4 14 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 169: ...Chapter 4 Transmission Subsystem TSS 4 17 ...
Страница 255: ...The HPTSS in 3745 Models 130 150 160 and 170 Data Flow Chapter 5 High Performance Transmission Subsystem HPTSS 5 3 ...
Страница 303: ...Figure 6 8 Ring to Ring via Bridge Example 2 Typical Multi Floor Wiring Chapter 6 The Token Ring Subsystem 6 9 ...
Страница 322: ...6 28 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 348: ...7 26 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 625: ...The ESS in 3745 Models 130 150 160 and 170 Data Flow Chapter 12 Ethernet Subsystem ESS 12 3 ...
Страница 668: ...Problem Determination Aid 12 46 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 674: ...X 6 IBM 3745 Models 130 150 160 170 and 17A Hardware Maintenance Reference ...
Страница 708: ......
Страница 711: ......
Страница 712: ...IBM Part Number 03F5010 Printed in Denmark by IBM Danmark A S ð3F5ð1ð SY33 2ð66 4 ...